Section 6

Troubleshooting

6.1Unit Will Not Start Or Starts Then Stops

Condition

Possible Cause

Remedy / Reference

No power to unit

External power source OFF

Turn On

Start-Stop switch OFF or defective

Check

Circuit breaker OFF or tripped

Check

Loss of control power

Circuit breaker OFF or defective

Check

Control transformer defective

Check

Fuse (F3A / F3B) blown

Check

Start-Stop switch OFF or defective

Check

Component(s) not operating

Evaporator fan motor internal protector open

Section 7.13

Gas Cooler fan motor internal protector open

Section 7.9

Compressor internal protector open

Section 7.3

High Pressure Switch (HPS) open

Section 5.8

Heat Termination Thermostat (HTT) open

Replace

Current sensor malfunction

Replace

6.2Unit Operates Long Or Continuously In Cooling

Condition

Possible Cause

Remedy / Reference

Container

Hot load

Normal

Box insulation defective or air leak

Repair

Refrigeration system

Refrigerant shortage

Section 7.2.6

Evaporator coil covered with ice

Section 6.6

Evaporator coil plugged with debris

Section 7.11

Evaporator coil has air bypass around it

Check

Controller set too low

Reset

Coil dirty

Section 7.8

Current limit (Cd32) set to wrong value

Section 4.4.3

Economizer Solenoid Valve (ESV) malfunction

Section 7.17

Electronic Expansion Valve (EEV)

Replace

6.3Unit Runs But Has Insufficient Cooling

Condition

Possible Cause

Remedy / Reference

Refrigeration system

Pressures abnormal

Section 6.7

Temperatures abnormal

Section 6.13

Currents abnormal

Section 6.14

Controller malfunction

Section 6.9

Evaporator fan or motor defective

Section 7.13

Electronic Expansion Valve (EEV)

Replace

 

6.4Unit Will Not Heat Or Has Insufficient Heating

Condition

Possible Cause

Remedy / Reference

No operation of any kind

Start-Stop switch OFF or defective

Check

Circuit breaker OFF or defective

Check

External power source OFF

ON

No control power

Circuit breaker or fuse defective

Replace

Control Transformer defective

Replace

Evaporator fan internal motor protector open

Section 7.13

Heat relay defective

Check

Heat Termination Thermostat (HTT) open

Section 7.11

Unit will not heat or has insufficient heat

Heater(s) defective

Section 7.11

Heater contactor or coil defective

Replace

Evaporator fan motor(s) defective

Section 7.11 / Section 7.13

Evaporator fan motor contactor defective

Replace

Controller malfunction

Section 6.9

Wiring defective

Replace

Terminal connections loose

Tighten

Line voltage low

Section 3.4

6.5Unit Will Not Terminate Heating

Condition

Possible Cause

Remedy / Reference

Unit fails to stop heating

Controller improperly set

Reset

Controller malfunction

Section 6.9

Heat Termination Thermostat (HTT) remains closed along with the heat relay

Section 7.11

 

6.6Unit Will Not Defrost Properly

Condition

Possible Cause

Remedy / Reference

Will not initiate defrost automatically

Defrost timer malfunction (Cd27)

Table 4–7

Terminal connections loose

Tighten

Wiring defective

Replace

Defrost Temperature Sensor (DTS) defective or Heat Termination Thermostat (HTT) open

Replace

Heater contactor or coil defective

Replace

Will not initiate defrost manually

Manual defrost switch defective

Replace

Keypad defective

Replace

Defrost Temperature Sensor (DTS) open

Replace

Initiates but relay DR drops out

Low line voltage

Section 3.4

Initiates but does not defrost

Heater contactor or coil defective

Replace

Heater(s) burned out

Section 7.11

6.7Abnormal Pressures

Condition

Possible Cause

Remedy / Reference

High discharge pressure

Gas Cooler coil dirty

Section 7.8

Gas Cooler fan rotating backwards

Section 7.9

Gas Cooler fan inoperative

Section 7.9

Refrigerant overcharge or non-condensibles

Section 7.2.6

High Pressure Expansion Valve (HPXV) control malfunction

Replace

Low suction pressure

Software incorrect and/or controller configuration incorrect

Check

Suction Pressure Transducer (SPT) failed

Replace

Evaporator air flow not present or restricted

Section 7.11

Electronic Expansion Valve (EEV) control malfunction

Replace

6.8Abnormal Noise Or Vibrations

Condition

Possible Cause

Remedy / Reference

Compressor

Mounting bolts loose

Tighten / Replace

Liquid slugging

Section 7.15

Gas Cooler or Evaporator Fan

Bent, loose or striking venturi

Check

Motor bearings worn

Section 7.9 / Section 7.13

Motor shaft bent

Section 7.9 / Section 7.13

 

 

6.9Microprocessor Malfunction

Condition

Possible Cause

Remedy / Reference

Will not control

Software incorrect and/or controller configuration incorrect

Check

Sensor defective

Section 7.22

Wiring defective

Check

Refrigerant charge low

Section 7.2.6

6.10No Evaporator Air Flow Or Restricted Air Flow

Condition

Possible Cause

Remedy / Reference

Evaporator coil blocked

Coil has frost

Section 6.6

Coil dirty

Section 7.11

No or partial evaporator air flow

Evaporator fan motor internal protector open

Section 7.13

Evaporator fan motor(s) defective

Section 7.13

Evaporator fan(s) loose or defective

Section 7.13

Evaporator fan contactor defective

Replace

6.11Electronic Expansion Valve (EEV) Malfunction

Condition

Possible Cause

Remedy / Reference

Low suction pressure

Software incorrect and/or controller configuration incorrect.

Check

Suction Pressure Transducer (SPT) failed

Replace

Evaporator air flow not present or restricted

Section 7.11

Evaporator coil has excessive frost

Section 6.6

Electronic Expansion Valve (EEV) control malfunction

Section 7.15

Evaporator Temperature Sensor (ETS) loose or insufficiently clamped

Replace

High suction pressure with low superheat

Valve contains foreign material

Section 6.11

Suction Pressure Transducer (SPT) failed

Replace

Electronic Expansion Valve (EEV) control malfunction

Replace

Liquid slugging in compressor

Suction Pressure Transducer (SPT) failed

Replace

Electronic Expansion Valve (EEV) failed

Replace

 

6.12High Pressure Expansion Valve (HPXV) Malfunction

Condition

Possible Cause

Remedy / Reference

High discharge pressure

High Pressure Expansion Valve (HPXV) coil not seated properly, loose, or not fully engaged.

Section 7.15.2

Software incorrect or controller configuration incorrect

Check

Discharge Pressure Transducer (DPT) failed

Replace

Filter drier restriction

Section 7.10

Gas Cooler Temperature Sensor (GCTS) loose or insufficiently clamped

Check

Gas cooler coil dirty

Section 7.8

Gas cooler fan rotating backwards

Section 7.9

Gas cooler fan inoperative

Section 7.9

HPXV control malfunction

Replace

HPXV failed

Replace

6.13Abnormal Temperatures

Condition

Possible Cause

Remedy / Reference

High discharge temperature

Gas cooler coil dirty

Section 7.8

Gas cooler fan rotating backwards

Section 7.9

Gas cooler fan inoperative

Section 7.9

Refrigerant overcharge or non-condensibles

Section 7.2.6

Electronic Expansion Valve (EEV) control malfunction

Replace

Suction Pressure Transducer (SPT) failed

Replace

Discharge Temperature Sensor drifting high

Replace

Sensor loose or insufficiently clamped

Replace

Electronic Solenoid Valve (ESV) coil not fully engaged

Section 7.17.2

ESV or ESV coil malfunction

Replace

6.14Abnormal Currents

Condition

Possible Cause

Remedy / Reference

Unit reads abnormal currents

Current sensor wiring

Check

Component is defective

Check current draw / Replace as needed.

6.15Fuse F1 or F2 Blown

Condition

Possible Cause

Remedy / Reference

Fuse F1 or F2 Blown

Electronic Expansion Valve (EEV) drive module wires were grounded.

Check EEV drive module by unplugging it, replacing the fuse(s) and turning the unit back on.