Section 3

Description

3.1General Description

3.1.1Refrigeration Unit - Front Section

The refrigeration unit is designed so that the majority of components are accessible from the front (see Figure 3.1).

3.1.2Fresh Air Makeup Vent

The function of the upper fresh air makeup vent is to provide ventilation for commodities that require fresh air circulation. The venting system / Vent Position Sensor (VPS) is located in the upper left access panel.

Figure 3.1  Refrigeration Unit - Front Section

fig3_uv.jpg 

1)Upper Fresh Air Makeup Vent Panel. Located inside are Evaporator Fan #2, Defrost Temperature Sensor (DTS)

2)Access Panel. Located inside are Evaporator Fan #1, Electronic Expansion Valve (EEV), Heat Termi­nation Thermostat (HTT)

3)Fork Lift Pockets

4)Control Box

5)Unit Display

6)Key Pad

7)Interrogator Connector (Front right)

8)Variable Frequency Drive (VFD)

9)Unit Nameplate: Serial Number, Model Number and Parts Identification Number (PID)

10)Power Cables & Plug location

11)Ambient Temperature Sensor (AMBS)

12)Unloader Solenoid Valve (USV)

13)Compressor

14)Flash Tank

15)Filter Drier

16)Gas Cooler Fan

17)TIR (Transports Internationaux Routiers) Sealing Provisions - Typical All Panels

- - - - -

3.1.3Evaporator Section

The two evaporator fans circulate air through the container by pulling air in from the top of the unit, directing the air through the evaporator coil where it is cooled or heated, and then discharging the conditioned air at the bottom of the unit.

Most evaporator components are accessible by removing the upper rear panel (as shown in Figure 3.2) or by removing the evaporator fan access panels (see Figure 3.1).

Figure 3.2  Evaporator Section

fig4_uv.jpg 

1)Evaporator Fan Motor #1 (EM1)

2)Evaporator Fan Motor #2 (EM2)

3)Return Recorder Sensor (RRS)
Return Temperature Sensor (RTS)

4)Humidity Sensor (HS)

5)Evaporator Coil

6)Evaporator Coil Heaters (Underside of Coil)

7)Heat Termination Thermostat (HTT)

8)Defrost Temperature Sensor (DTS)

9)Evaporator Temperature Sensor (ETS1)

10)Interrogator Connector (Rear) (ICR)

11)USDA Probe Receptacle PR2

12)USDA Probe Receptacle PR1

13)USDA Probe Receptacle PR3

14)Cargo Probe Receptacle PR4

15)Electronic Expansion Valve (EEV)

- - - - -

3.1.4Compressor and Flash Tank Section

Figure 3.3  Compressor and Flash Tank Section - PIDs lower than NT5010

fig_compressor-section-original.jpg 

1)Compressor

2)Compressor Discharge Temperature Sensor (CPDS)

3)High Pressure Relief Valve (HPRV)

4)High Pressure Switch (HPS)

5)Gas Cooler Temperature Sensor (GCTS)

6)High Side Service Connection

7)Discharge Pressure Transducer (DPT)

8)Filter Drier

9)High Pressure Expansion Valve (HPXV)

10)Flash Tank

11)Flash Tank Pressure Relief Valve (FTPRV)

12)Flash Tank Pressure Transducer (FPT)

13)Economizer Solenoid Valve (ESV)

14)Unloader Solenoid Valve (USV)

15)Low Pressure Relief Valve (LPRV)

16)Low Side Service Connection

17)Suction Pressure Transducer (SPT)

18)Ambient Temperature Sensor (AMBS)

19)Supply Recorder Sensor (SRS)

20)Supply Temperature Sensor (STS)

- - - - -

Figure 3.4  Compressor and Flash Tank Section - PIDs NT5010 and higher

fig_compressor-section-NT5010.jpg 

1)Compressor

2)Compressor Discharge Temperature Sensor (CPDS)

3)High Pressure Relief Valve (HPRV)

4)High Pressure Switch (HPS)

5)Discharge Pressure Transducer (DPT)

6)Gas Cooler Temperature Sensor (GCTS)

7)High Side Service Connection

8)Filter Drier

9)High Pressure Expansion Valve (HPXV)

10)Flash Tank

11)Flash Tank Pressure Relief Valve (FTPRV)

12)Flash Tank Pressure Transducer (FPT)

13)Economizer Solenoid Valve (ESV)

14)Unloader Solenoid Valve (USV)

15)Low Pressure Relief Valve (LPRV)

16)Low Side Service Connection

17)Suction Pressure Transducer (SPT)

18)Ambient Temperature Sensor (AMBS)

19)Supply Recorder Sensor (SRS)

20)Supply Temperature Sensor (STS)

- - - - -

Figure 3.5  Compressor Detail

Description00018.jpg 

1)Variable Frequency Drive (VFD)

2)Compressor Terminal Box

3)Moisture Indicator / Sight Glass (if equipped)

4)Oil Drain Port

5)Oil Pump

6)First Stage Discharge Port / Flange

7)Second Stage Suction Port / Flange

8)Second Stage Discharge Port / Flange

9)Cylinder Head

10)Suction Pressure Transducer (SPT)

11)Suction Port / Flange

12)Compressor Motor End Cover

13)Service Connection, Suction

14)Compressor Mounting Bolts

15)Compressor Serial / Model Number Plate

- - - - -

3.1.5Gas Cooler / Intercooler

The gas cooler / intercooler coil acts as a heat exchanger in which compressed refrigerant gas from the compressor is lowered in temperature as it circulates through the coil tubes. The gas cooler / intercooler fan pulls external, ambient air through all four sides of the coil, heat from the refrigerant is transferred to the air, and then the warm air is discharged horizontally through the front of the fan grille.

Figure 3.6  Gas Cooler / Intercooler

fig7_uv.jpg 

1)Gas Cooler Fan

2)Gas Cooler Fan Motor

3)Gas Cooler Coil

4)Gas Cooler Coil Cover

5)Gas Cooler Inlet

6)Gas Cooler Outlet

7)Intercooler Inlet

8)Intercooler Outlet

- - - - -

3.1.6Control Box Section

Figure 3.7  Control Box Section

fig9_uv.jpg 

1)Compressor Contactor - CH

2)Phase A Contactor - PA

3)Phase B Contactor - PB

4)Heater Contactor - HR

5)Communications Interface Module

6)Controller / DataCORDER Module (Controller)

7)Variable Frequency Interface Module (VIM)

8)Display Module

9)Keypad

10)Controller Battery Pack standard location

11)Start - Stop Switch, ST

12)Interrogator Connector Box location

13)Control Transformer

14)High Speed Evap. Fan Contactor - EF

15)Low Speed Evap. Fan Contactor - ES

16)High Speed Gas Cooler Fan Contactor - GF

17)Low Speed Gas Cooler Fan Contactor - GS

18)Circuit Breaker (CB-1) - 25 Amps

19)Current Sensor Module

20)Ferrite Core

- - - - -

3.1.7Communications Interface Module

The optional communications interface module (see Figure 3.7) is a slave module that allows communication with a master central monitoring station. The module will respond to communication and return information over the main power line. Refer to the master central monitoring station technical manual for additional information.

3.1.8Water-Cooled Condenser Section

The water-cooled condenser section (Figure 3.8) consists of a water-cooled condenser, water couplings, and a water pressure switch.

Figure 3.8  Water-Cooled Condenser

Fig_wcc.png 

1)Water-Cooled Condenser

2)Coupling (Water In)

3)Self Draining Coupling (Water Out)

4)Water Pressure Switch (WP)

- - - - -

3.2Refrigeration System Data

Compressor / Motor Assembly

Weight (With Oil)

158 kg (348 lb)

Approved Oil

Carrier P/N 46-00025-06

Idemitsu FVC 100D

Oil Charge

2000 ml (67 ounces)

Oil Sight Glass (Service Compressor Only)

The oil level range, while the unit operating, should be between 1/4 and 3/4 level of the sight glass.

Electronic Expansion Valve Superheat (Evaporator)

Variable

High Pressure Expansion Valve (HPXV)

Variable

Heater Termination Thermostat (HTT)

Opens

54°(+/- 3) C& = 130°(+/- 5) F

Closes

38°(+/- 4) C = 100°(+/- 7) F

High Pressure Switch (HPS)

Cut-Out

138 (+7/-11) bar = 2000 (+100/-156) psig

Cut-In

99 (+/- 10) bar = 1430 (+/- 140) psig

Charge according to nameplate specifications to ensure optimal unit performance.

Refrigerant Charge - R-744

Unit Configuration

Charge Requirements

99.9% pure & CO2 with maximum 10 ppm of water (AHRI 700)

For servicing, charge to 9.5 lbs / 4.31kg.
Also refer to nameplate, see Figure 2.2 

Pressure Relief Valves - Set Pressure

PIDs lower than NT5010

Opens, Low Side

89.6 bar = 1300 psig

Opens, Flash Tank

108.2 bar = 1569 psig

Opens, High Side

150.9 bar = 2189 psig

 

PIDs NT5010 and higher

Opens, Low Side

89.6 bar = 1300 psig

Opens, Flash Tank

117.2 bar = 1700 psig

Opens High Side

150.9 bar = 2189 psig

Unit Weight

Refer to nameplate, see Figure 2.2

Water Pressure Switch (WP)

Cut-In

0.5 + 0.2 kg/cm3 (7 + 3 psig)

Cut-Out

1.6 + 0.4 kg/cm3 (22 + 5 psig)

3.3Torque Requirements

 

Pressure Relief Valves

 

PIDs lower than NT5010

Low Side Pressure Relief Valve (LPRV)

88.1-96.3 Nm (65-71 ft-lb)

Flash Tank Pressure Relief Valve (FTPRV)

29.8-32.5 Nm (22-24 ft-lb)

High Side Pressure Relief Valve (HPRV)

51.5-56.9 Nm (38-42 ft-lb)

PIDs NT5010 and higher

Low Side Pressure Relief Valve (LPRV)

77.3-85.4 Nm (57-63 ft-lb)

Flash Tank Pressure Relief Valve (FTPRV)

29.8-32.5 Nm (22-24 ft-lb)

High Side Pressure Relief Valve (HPRV)

51.5-56.9 Nm (38-42 ft-lb)

Pressure Transducers

PIDs lower than NT5010

Suction Pressure Transducer (SPT)

25.7-28.5 Nm (19-21 ft-lb)

Flash Tank Pressure Transducer (FPT)

9.5-12.2 Nm (7-8 ft-lb)

Discharge Pressure Transducer (DPT)

9.5-12.2 Nm (7-8 ft-lb)

Service Fittings / Service Valves

PIDs lower than NT5010

Suction Service Fitting

25.7-28.5 Nm (19-21 ft-lb)

Discharge Service Fitting

9.5-12.2 Nm (7-8 ft-lb)

PIDs NT5010 and higher

Suction or Discharge Service Valve

 

Top Cap

10-14 Nm (7-10 ft-lb)

Stem, Open

Max. 2 Nm (1.5 ft-lb)

Stem, Closed

6-8 Nm (4-6 ft-lb)

Flare Cap

10-14 Nm (7-10 ft-lb)

Filter Drier

Filter Drier

18.4-22.1 Nm (25-30 ft-lb)

Pressure Switch

High Pressure Switch

17.6-19 Nm (13-14 ft-lb)

Bolts

Compressor Flange Bolts

35.3-38 Nm (26-28 ft-lb)

3.4Electrical System Data

Circuit Breaker

CB-1

25 amps

Compressor Motor

Full Load Amps (FLA)

13 amps @ 460 VAC

Gas Cooler Fan Motor

Nominal Supply

380 VAC, 3 Phase,

50 Hz +/- 2.5% Hz

460 VAC, 3 Phase,

60 Hz +/- 2.5% Hz

Full Load Amps, High Speed

1.10 amps

1.20 amps

Full Load Amps, Low Speed

0.68 amps

0.69 amps

Horsepower, High Speed

0.35 hp

0.60 hp

Horsepower, Low Speed

0.04 hp

0.06 hp

RPM, High Speed

1450 rpm

1725 rpm

RPM, Low Speed

700 rpm

825 rpm

Voltage

360 - 460 VAC

400 - 500 VAC

Bearing Lubrication

Factory lubricated, additional grease not required.

Rotation

Counter-clockwise when viewed from shaft end.

Evaporator Coil Heaters

Number of Heaters

6

Rating

750 watts +/- 5% each @ 230 VAC

Resistance (cold)

72 ohms +/- 5% @ 20°C (68°F)

Type

Sheath

Evaporator Fan Motors

Nominal Supply

380 VAC, 3 Phase,

50 Hz +/- 2.5% Hz

460 VAC, 3 Phase,

60 Hz +/- 2.5% Hz

Full Load Amps High Speed

1.07

0.9

Full Load Amps Low Speed

0.47

0.47

Nominal Horsepower High Speed

0.36

0.63

Nominal Horsepower Low Speed

0.05

0.08

Rotations Per Minute High Speed

2850 rpm

3450 rpm

Rotations Per Minute Low Speed

1425 rpm

1725 rpm

Voltage

360 - 460 VAC

400 - 500 VAC

Bearing Lubrication

Factory lubricated, additional grease not required

Rotation

CW when viewed from shaft end

Fuses

Control Circuit

7.5 amps (F3A, F3B)

Controller / DataCORDER

5 amps (F1, F2)

Vent Position Sensor (VPS)

Electrical Output

0.5 VDC to 4.5 VDC over 90 degree range

Supply Voltage

5 VDC +/- 10%

Supply Current

5 mA (typical)

Solenoid Valve Coils (ESV/USV) 24 VAC

Nominal Resistance @ 20° C (68°F)

12.4 ohms +/- 5%

Maximum Current Draw

0.7 amps

Electronic Expansion Valve (EEV)

Nominal Resistance

100 ohms A-B and C-D

Supply Voltage

12 VDC +/- 10%

High Pressure Expansion Valve (HPXV)

Nominal Resistance

30 ohms from Ground / Common 1 to 2, 3, 4 and 5 on the KE plug

Supply Voltage

12 VDC +/- 10%

Variable Frequency Drive (VFD)

460 Volts

Variable Frequency

Humidity Sensor (HS)

Orange wire

Power

Red wire

Output

Brown wire

Ground

Input voltage

5 VDC

Output voltage

0 to 3.3 VDC

Output voltage readings verses relative humidity (RH) percentage:

30%

0.99 V

50%

1.65 V

70%

2.31 V

90%

2.97 V

Controller

Setpoint Range

-40 to +30°C (-40 to +86°F)

3.5Safety and Protective Devices

Unit components are protected from damage by safety and protective devices listed in Table 3–1. These devices monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition occurs.

Open safety switch contacts on either or both of devices IP-CP or HPS will shut down the compressor.

Open safety switch contacts on device IP-CM will shut down the Gas Cooler fan motor.

The entire refrigeration unit will shut down if one of the following safety devices open: (a) circuit breaker(s); (b) fuse (F3A / F3B, 7.5A); or (c) evaporator fan motor internal protector(s) - (IP).

Table 3–1  Safety and Protective Devices

Unsafe Condition

Device

Device Setting

Excessive current draw

Circuit Breaker (CB-1) - Manual Reset

Trips at 25 amps (460 VAC)

Excessive current draw in the control circuit

Fuse (F3A & F3B)

7.5 amp rating

Excessive current draw by the controller Fuse

Fuse (F1 & F2)

5 amp rating

Excessive Gas Cooler fan motor winding temperature

Internal Protector (IP-CM) - Automatic Reset

N/A

Excessive compressor motor winding temperature

Internal Protector (IP-CP) - Automatic Reset

N/A

Excessive evaporator fan motor(s) winding temperature

Internal Protector(s) (IP-EM) - Automatic Reset

N/A

Abnormal pressures in the refrigerant system

Low Side PRV

89.6 bar = 1300 psig

Flash Tank PRV

108.2 bar = 1569 psig

High Side PRV

150.9 bar = 2189 psig

Abnormally high discharge pressure

High Pressure Switch (HPS), Cut-Out

138 (+7/-11) bar = 2000 (+100/-156) psig

High Pressure Switch (HPS), Cut-In

99 (+/- 10) bar = 1430 (+/- 140) psig

3.6Refrigeration Circuit

The NaturaLINE unit operates as a vapor compression refrigeration system using R-744 (CO2) as the refrigerant. The main components of the system are a Reciprocating Compressor, Gas Cooler/Intercooler, High Pressure Expansion Valve (HPXV), Flash Tank, Electronic Expansion Valve (EEV), Economizer Solenoid Valve (ESV), Unloader Solenoid Valve (USV) and an Evaporator.

The refrigeration system operates in one of three modes; Standard, Unloaded, or Economized. At system start up, and during periods of low refrigeration load, the unit will operate in Unloaded Mode. This allows the microprocessor to place the system in operation at reduced capacity in order to measure the actual load. If the microprocessor determines that further capacity is required, such as periods of high load or pull down, the system will transition to Economized Mode. Standard Mode is used to maintain temperature during stable load conditions.

3.6.1Standard Mode

At the compressor, the CO2 refrigerant is drawn in at the suction port and compressed into a higher pressure, higher temperature gas. The compressed gas exits the first stage of the Compressor, enters the Intercooler, then returns back to the Compressor at the second stage suction port, where the gas is compressed to a higher pressure and higher temperature. The compressed gas then exits the Compressor at the discharge port and flows through the Gas Cooler. Discharge temperature of the refrigerant is continuously monitored by the Compressor Discharge Temperature Sensor (CPDS).

As refrigerant travels through the tubes in the Gas Cooler, ambient air flowing across the coil fins and tubes removes heat from the refrigerant gas. As heat from the refrigerant is transferred to the ambient air, the refrigerant gas cools and then passes through the Filter Drier. The Filter Drier ensures that the refrigerant is clean and dry.

The flow of refrigerant from the Filter Drier to the Flash Tank is regulated by the High Pressure Expansion Valve (HPXV). The HPXV is controlled by the operating software for optimal performance and efficiency. As the microprocessor receives temperature and pressure data, the HPXV stepper motor will open or close in order to control and maintain maximum system efficiency. As refrigerant flows through the variable orifice of the HPXV, the reduced pressure causes the refrigerant to flash (flash gas) while entering the Flash Tank. In the Flash Tank, vapor and liquid are separated.

The liquid refrigerant from the Flash Tank continues through the liquid line to the Electronic Expansion Valve (EEV). The EEV is used to control the superheat of the refrigerant leaving the Evaporator. As the microprocessor receives suction pressure and temperature data, the microprocessor transmits electronic pulses to the EEV stepper motor which opens or closes the variable valve orifice in order to control and maintain proper superheat. Superheat is controlled to ensure that liquid refrigerant never enters the compressor.

The liquid refrigerant flows through the Evaporator, absorbing heat from the return air as the return air flows across the fins and tubes of the Evaporator coil. As the liquid refrigerant in the Evaporator coil absorbs heat, the refrigerant vaporizes, and the vapor flows through the suction port back to the compressor.

3.6.2First Stage Discharge Port & Suction Port

The high pressure, high temperature refrigerant that is discharged from the first stage discharge port flows directly to the Intercooler section of the Gas Cooler / Intercooler. As the refrigerant travels through the tubes in the Intercooler, ambient air flowing across the coil fins and tubes removes heat, cooling but not condensing the gas. The refrigerant leaving the Intercooler flows to three locations: the check valve (where it is stopped), the Unloader Solenoid Valve (USV) (which is normally closed in Standard and Economized Mode), and to the mid-stage suction port where refrigerant returns to the Compressor.

3.6.3Unloaded Mode

During system start up and periods of low cooling load, the unit will operate in Unloaded Mode to conserve energy. In Unloaded Mode, the normally closed USV opens. While in Unloaded Mode, a portion of the refrigerant leaving the Intercooler is redirected to the suction port, back to the Compressor. The remaining portion of the refrigerant leaving the Intercooler continues to the second stage suction port. To further reduce cooling, the Variable Frequency Drive (VFD) may reduce Compressor speed.

3.6.4Economized Mode

In Economized Mode, the main refrigeration system operates the same as in Standard Mode, except the microprocessor energizes (opens) the Economizer Solenoid Valve (ESV). When the ESV is open, frozen and pull down capacity of the unit is increased by allowing refrigerant vapor to flow from the Flash Tank through the check valve, and to the mid-stage suction port where the refrigerant returns to the Compressor. During Economized Mode, the USV will remained closed.

3.6.5Electronic Expansion Valve (EEV)

The microprocessor controls the superheat of refrigerant leaving the evaporator by opening and closing the variable orifice in the EEV. The microprocessor transmits electronic pulses to the EEV stepper motor, which opens or closes the valve orifice to maintain superheat. EEV control is based on inputs from the Suction Pressure Transducer (SPT) and the Evaporator Temperature Sensor (ETS).

Figure 3.9  Refrigeration Circuit Schematic - PIDs lower than NT5010

fig-refrigeration-circuit.png 

1)Compressor

2)Intercooler

3)Compressor Discharge Temperature Sensor (CPDS)

4)High Pressure Relief Valve (HPRV)

5)High Pressure Safety Switch (HPS)

6)Gas Cooler

7)Gas Cooler Temperature Sensor (GCTS)

8)Discharge Pressure Transducer (DPT)

9)High Side Service Fitting

10)Filter Drier

11)High Pressure Expansion Valve (HPXV)

12)Flash Tank

13)Flash Tank Pressure Relief Valve (FTPRV)

14)Flash Tank Pressure Transducer (FPT)

15)Economizer Solenoid Valve (ESV)

16)Electronic Expansion Valve (EEV)

17)Evaporator

18)Evaporator Temperature Sensor (ETS)

19)Low Pressure Relief Valve (LPRV)

20)Unloader Solenoid Valve (USV)

21)Suction Pressure Transducer (SPT), located on back of compressor

22)Low Side Service Fitting

23)Filter Screens

- - - - -

Figure 3.10  Refrigeration Circuit Schematic - PIDs NT5010 and higher

fig-refrigeration-circuit-5010.png 

1)Compressor

2)Intercooler

3)Compressor Discharge Temperature Sensor (CPDS)

4)High Pressure Relief Valve (HPRV)

5)High Pressure Safety Switch (HPS)

6)Gas Cooler

7)Gas Cooler Temperature Sensor (GCTS)

8)Discharge Pressure Transducer (DPT)

9)High Side Service Valve

10)Filter Drier

11)High Pressure Expansion Valve (HPXV)

12)Flash Tank

13)Flash Tank Pressure Relief Valve (FTPRV)

14)Flash Tank Pressure Transducer (FPT)

15)Economizer Solenoid Valve (ESV)

16)Electronic Expansion Valve (EEV)

17)Evaporator

18)Evaporator Temperature Sensor (ETS)

19)Low Pressure Relief Valve (LPRV)

20)Unloader Solenoid Valve (USV)

21)Suction Pressure Transducer (SPT)

22)Low Side Service Valve

23)Filter Screens

- - - - -

Figure 3.11  Refrigeration Circuit Schematic (WCC) - PIDs lower than NT5010

fig-refrigeration-circuit-wcc.png 

1)Compressor

2)Intercooler

3)Compressor Discharge Temperature Sensor (CPDS)

4)High Side Pressure Relief Valve (HPRV)

5)High Pressure Safety Switch (HPS)

6)Water Cooled Condenser (WCC)

7)Water Pressure Switch (WPS)

8)Gas Cooler

9)Gas Cooler Temperature Sensor (GCTS)

10)Discharge Pressure Transducer (DPT)

11)High Side Service Fitting

12)Filter Drier

13)High Pressure Expansion Valve (HPXV)

14)Flash Tank

15)Flash Tank Pressure Relief Valve (FTPRV)

16)Flash Tank Pressure Transducer (FPT)

17)Economizer Solenoid Valve (ESV)

18)Electronic Expansion Valve (EEV)

19)Evaporator

20)Evaporator Temperature Sensor (ETS)

21)Low Side Pressure Relief Valve (LPRV)

22)Unloader Solenoid Valve (USV)

23)Suction Pressure Transducer (SPT)

24)Low Side Service Fitting

25)Filter Screens

- - - - -

Figure 3.12  Refrigeration Circuit Schematic (WCC) - PIDs NT5010 and higher

fig-refrigeration-circuit-wcc-5010.png 

1)Compressor

2)Intercooler

3)Compressor Discharge Temperature Sensor (CPDS)

4)High Side Pressure Relief Valve (HPRV)

5)High Pressure Safety Switch (HPS)

6)Water Cooled Condenser (WCC)

7)Water Pressure Switch (WPS)

8)Gas Cooler

9)Gas Cooler Temperature Sensor (GCTS)

10)Discharge Pressure Transducer (DPT)

11)High Side Service Valve

12)Filter Drier

13)High Pressure Expansion Valve (HPXV)

14)Flash Tank

15)Flash Tank Pressure Relief Valve (FTPRV)

16)Flash Tank Pressure Transducer (FPT)

17)Economizer Solenoid Valve (ESV)

18)Electronic Expansion Valve (EEV)

19)Evaporator

20)Evaporator Temperature Sensor (ETS)

21)Low Side Pressure Relief Valve (LPRV)

22)Unloader Solenoid Valve (USV)

23)Suction Pressure Transducer (SPT)

24)Low Side Service Valve

25)Filter Screens

- - - - -