Section 6
Condition |
Possible Cause |
Remedy / Reference |
---|---|---|
No power to unit |
External power source OFF |
Turn on |
Start-Stop switch OFF or defective |
Check |
|
Circuit breaker tripped or OFF |
Check |
|
Loss of control power |
Circuit breaker OFF or defective |
Check |
Control transformer defective |
Replace |
|
Fuse (F3A/F3B) blown |
Check |
|
Start-Stop switch OFF or defective |
Check |
|
Component(s) not operating |
Evaporator fan motor internal protector open |
|
Condenser fan motor internal protector open |
||
Compressor internal protector open |
||
High pressure switch open |
||
Heat termination thermostat open |
Replace |
|
Malfunction of current sensor |
Replace |
|
Compressor hums, but does not start |
Low line voltage |
Check |
Single phasing |
Check |
|
Shorted or grounded motor windings |
||
Compressor seized |
||
Container |
Hot load |
Normal |
Defective box insulation or air leak |
Repair |
|
Refrigeration system |
Shortage of refrigerant |
|
Evaporator coil covered with ice |
||
Evaporator coil plugged with debris |
||
Evaporator fan(s) rotating backwards |
||
Air bypass around evaporator coil |
Check |
|
Controller set too low |
Reset |
|
Compressor service valves or liquid line shutoff valve partially closed |
Open valves completely |
|
Dirty condenser |
||
Compressor worn |
||
Current limit (function code Cd32) set to wrong value |
||
Economizer solenoid valve malfunction |
||
Digital unloader valve stuck open |
Replace |
|
Electronic expansion valve |
Replace |
|
Refrigeration system |
Abnormal pressures |
|
Abnormal temperatures |
||
Abnormal currents |
||
Controller malfunction |
||
Evaporator fan or motor defective |
||
Compressor service valves or liquid line shutoff valve partially closed |
Open valves completely |
|
Frost on coil |
||
Digital unloader valve stuck open |
Replace |
|
Electronic expansion valve |
Replace |
|
No operation of any kind |
Start-Stop switch OFF or defective |
Check |
Circuit breaker OFF or defective |
Check |
|
External power source OFF |
Turn ON |
|
No control power |
Circuit breaker or fuse defective |
Replace |
Control Transformer defective |
Replace |
|
Evaporator fan internal motor protector open |
||
Heat relay defective |
Check |
|
Heater termination thermostat open |
||
Unit will not heat or has insufficient heat |
Heater(s) defective |
|
Heater contactor or coil defective |
Replace |
|
Evaporator fan motor(s) defective or rotating backwards |
||
Evaporator fan motor contactor defective |
Replace |
|
Controller malfunction |
||
Defective wiring |
Replace |
|
Loose terminal connections |
Tighten |
|
Low line voltage |
||
Unit fails to stop heating |
Controller improperly set |
Reset |
Controller malfunction |
||
Heater termination thermostat remains closed along with the heat relay |
||
Will not initiate defrost automatically |
Defrost timer malfunction (Cd27) |
|
Loose terminal connections |
Tighten |
|
Defective wiring |
Replace |
|
Defrost temperature sensor defective or heat termination thermostat open |
Replace |
|
Heater contactor or coil defective |
Replace |
|
Will not initiate defrost manually |
Manual defrost switch defective |
Replace |
Keypad is defective |
Replace |
|
Defrost temperature sensor open |
Replace |
|
Initiates but relay (DR) drops out |
Low line voltage |
|
Initiates but does not defrost |
Heater contactor or coil defective |
Replace |
Heater(s) burned out |
||
Frequent defrost |
Wet load |
Normal |
High discharge pressure |
Condenser coil dirty |
|
Condenser fan rotating backwards |
||
Condenser fan inoperative |
||
Refrigerant overcharge or non-condensibles |
||
Discharge service valve partially closed |
Open |
|
Electronic expansion valve (EEV) control malfunction |
Replace |
|
Low suction pressure |
Incorrect software and/or controller configuration |
Check |
Failed suction pressure transducer (SPT) or evaporator pressure transducer (EPT) |
Replace |
|
Suction service valve partially closed |
Open |
|
Filter drier partially plugged |
||
Low refrigerant charge |
||
No evaporator air flow or restricted air flow |
||
Excessive frost on evaporator coil |
||
Evaporator fan(s) rotating backwards |
||
EEV control malfunction |
Replace |
|
Failed digital unloader valve (DUV) |
Replace |
|
Suction and discharge pressures tend to equalize when unit is operating |
Compressor operating in reverse |
|
Compressor cycling/stopped |
Check |
|
Failed digital unloader valve (DUV) |
Replace |
|
Compressor |
Compressor start up after an extended shutdown |
Normal |
Brief chattering when manually shut down |
||
Compressor operating in reverse |
||
Loose mounting bolts or worn resilient mounts |
Tighten/ Replace |
|
Loose upper mounting |
||
Liquid slugging |
||
Condenser or Evaporator Fan |
Bent, loose or striking venturi |
Check |
Worn motor bearings |
||
Bent motor shaft |
||
Will not control |
Incorrect software and/or controller configuration |
Check |
Defective sensor |
||
Defective wiring |
Check |
|
Low refrigerant charge |
||
Evaporator coil blocked |
Frost on coil |
|
Dirty coil |
||
No or partial evaporator air flow |
Evaporator fan motor internal protector open |
|
Evaporator fan motor(s) defective |
||
Evaporator fan(s) loose or defective |
||
Evaporator fan contactor defective |
Replace |
|
Low suction pressure |
Incorrect software and/or controller configuration |
Check |
Failed suction pressure transducer (SPT), or evaporator pressure transducer (EPT) |
Replace |
|
Suction service valve partially closed |
Open |
|
Filter drier partially plugged |
||
Low refrigerant charge |
||
No evaporator air flow or restricted air flow |
||
Excessive frost on evaporator coil |
||
Evaporator fan(s) rotating backwards |
||
EEV control malfunction |
||
Failed digital unloader valve (DUV) |
Replace |
|
Loose or insufficiently clamped sensor |
Replace |
|
High suction pressure with low superheat |
Foreign material in valve |
|
Failed suction pressure transducer (SPT), or evaporator pressure transducer (EPT) |
Replace |
|
EEV control malfunction |
Replace |
|
Improperly seated powerhead |
Ensure power head is locked and in place |
|
Liquid slugging in compressor |
Failed suction pressure transducer (SPT), or evaporator pressure transducer (EPT) |
Replace |
Failed EEV |
Replace |
|
The compressor may start in reverse for up to 10 seconds to determine correct phase rotation if required for phase detection. Allowing the scroll compressor to operate in reverse for more than two minutes will result in internal compressor damage. Turn the start-stop switch OFF immediately. |
||
Electrical |
Incorrect wiring of compressor |
Check |
Incorrect wiring of compressor contactor(s) |
||
Incorrect wiring of current sensor |
||
High discharge temperature |
Condenser coil dirty |
|
Condenser fan rotating backwards |
||
Condenser fan inoperative |
||
Refrigerant overcharge or non-condensibles |
||
Discharge service valve partially closed |
Open |
|
Electronic expansion valve (EEV) control malfunction |
Replace |
|
Failed suction pressure transducer (SPT), or evaporator pressure transducer (EPT) |
Replace |
|
Discharge temperature sensor drifting high |
Replace |
|
Failed economizer expansion valve, economizer coil, or economizer solenoid valve |
Replace |
|
Plugged economizer expansion valve, economizer coil, or economizer solenoid valve |
Replace |
|
Loose or insufficiently clamped sensor |
Replace |
|
Unit reads abnormal currents |
Current sensor wiring |
Check |