Section 6

TROUBLESHOOTING

 

Condition

Possible Cause

Remedy /

Reference

6.1Unit will not Start or Starts then Stops

No power to unit

External power source OFF

Turn on

Start-Stop switch OFF or defective

Check

Circuit breaker tripped or OFF

Check

Loss of control power

Circuit breaker OFF or defective

Check

Control transformer defective

Replace

Fuse (F3A/F3B) blown

Check

Start-Stop switch OFF or defective

Check

Component(s) not operating

Evaporator fan motor internal protector open

7.10

Condenser fan motor internal protector open

7.7

Compressor internal protector open

7.4

High pressure switch open

6.7

Heat termination thermostat open

Replace

Malfunction of current sensor

Replace

Compressor hums,

but does not start

Low line voltage

Check

Single phasing

Check

Shorted or grounded motor windings

7.4

Compressor seized

7.4

6.2Unit Operates Long or Continuously in Cooling

Container

Hot load

Normal

Defective box insulation or air leak

Repair

Refrigeration system

Shortage of refrigerant

7.3

Evaporator coil covered with ice

6.6

Evaporator coil plugged with debris

7.9

Evaporator fan(s) rotating backwards

7.9 / 7.10

Air bypass around evaporator coil

Check

Controller set too low

Reset

Compressor service valves or liquid line

shutoff valve partially closed

Open valves completely

Dirty condenser

7.6

Compressor worn

7.4

Current limit (function code Cd32) set to wrong value

4.4.3

Economizer solenoid valve malfunction

7.16

Digital unloader valve stuck open

Replace

Electronic expansion valve

Replace

6.3Unit Runs but has Insufficient Cooling

Refrigeration system

Abnormal pressures

6.7

Abnormal temperatures

6.13

Abnormal currents

6.14

Controller malfunction

6.9

Evaporator fan or motor defective

7.10

Compressor service valves or liquid line

shutoff valve partially closed

Open valves completely

Frost on coil

6.10

Digital unloader valve stuck open

Replace

Electronic expansion valve

Replace

6.4Unit will not Heat or has Insufficient Heating

No operation of any kind

Start-Stop switch OFF or defective

Check

Circuit breaker OFF or defective

Check

External power source OFF

Turn ON

No control power

Circuit breaker or fuse defective

Replace

Control Transformer defective

Replace

Evaporator fan internal motor protector open

7.10

Heat relay defective

Check

Heater termination thermostat open

7.9

Unit will not heat or

has insufficient heat

Heater(s) defective

7.9

Heater contactor or coil defective

Replace

Evaporator fan motor(s) defective or rotating backwards

7.9 / 7.10 

Evaporator fan motor contactor defective

Replace

Controller malfunction

6.9

Defective wiring

Replace

Loose terminal connections

Tighten

Low line voltage

3.3

6.5Unit will not Terminate Heating

Unit fails to stop heating

Controller improperly set

Reset

Controller malfunction

6.9

Heater termination thermostat remains closed

along with the heat relay

7.9

6.6Unit will not Defrost Properly

Will not initiate defrost

automatically

Defrost timer malfunction (Cd27)

Table 4–5

Loose terminal connections

Tighten

Defective wiring

Replace

Defrost temperature sensor defective or heat

termination thermostat open

Replace

Heater contactor or coil defective

Replace

Will not initiate

defrost manually

Manual defrost switch defective

Replace

Keypad is defective

Replace

Defrost temperature sensor open

Replace

Initiates but relay

(DR) drops out

Low line voltage

 3.3

Initiates but does not defrost

Heater contactor or coil defective

Replace

Heater(s) burned out

7.9

Frequent defrost

Wet load

Normal

6.7Abnormal Pressures

High discharge pressure

Condenser coil dirty

7.6

Condenser fan rotating backwards

7.7

Condenser fan inoperative

7.7

Refrigerant overcharge or non-condensibles

7.3

Discharge service valve partially closed

Open

Electronic expansion valve (EEV) control malfunction

Replace

Low suction pressure

Incorrect software and/or controller configuration

Check

Failed suction pressure transducer (SPT) or evaporator pressure transducer (EPT)

Replace

Suction service valve partially closed

Open

Filter drier partially plugged

7.8

Low refrigerant charge

 7.3

No evaporator air flow or restricted air flow

7.9

Excessive frost on evaporator coil

6.6

Evaporator fan(s) rotating backwards

7.10.3

EEV control malfunction

Replace

Failed digital unloader valve (DUV)

Replace

Suction and discharge

pressures tend to equalize when unit is operating

Compressor operating in reverse

6.12

Compressor cycling/stopped

Check

Failed digital unloader valve (DUV)

Replace

6.8Abnormal Noise or Vibrations

Compressor

Compressor start up after an extended shutdown

Normal

Brief chattering when manually shut down

Compressor operating in reverse

6.12

Loose mounting bolts or worn resilient mounts

Tighten/

Replace

Loose upper mounting

 7.4.1

Liquid slugging

7.12

Condenser or

Evaporator Fan

Bent, loose or striking venturi

Check

Worn motor bearings

7.7 / 7.10 

Bent motor shaft

7.7 / 7.10 

6.9Microprocessor Malfunction

Will not control

Incorrect software and/or controller configuration

Check

Defective sensor

7.19

Defective wiring

Check

Low refrigerant charge

 7.3

6.10No Evaporator Air Flow or Restricted Air Flow

Evaporator coil blocked

Frost on coil

6.6

Dirty coil

7.9

No or partial

evaporator air flow

Evaporator fan motor internal protector open

7.10

Evaporator fan motor(s) defective

7.10

Evaporator fan(s) loose or defective

7.10

Evaporator fan contactor defective

Replace

6.11Electronic Expansion Valve Malfunction

Low suction pressure

Incorrect software and/or controller configuration

Check

Failed suction pressure transducer (SPT),

or evaporator pressure transducer (EPT)

Replace

Suction service valve partially closed

Open

Filter drier partially plugged

7.8

Low refrigerant charge

 7.3

No evaporator air flow or restricted air flow

7.9

Excessive frost on evaporator coil

6.6

Evaporator fan(s) rotating backwards

7.10.3

EEV control malfunction

6.11

Failed digital unloader valve (DUV)

Replace

Loose or insufficiently clamped sensor

Replace

High suction pressure

with low superheat

Foreign material in valve

6.11

Failed suction pressure transducer (SPT),

or evaporator pressure transducer (EPT)

Replace

EEV control malfunction

Replace

Improperly seated powerhead

Ensure power head is locked and in place

Liquid slugging in

compressor

Failed suction pressure transducer (SPT),

or evaporator pressure transducer (EPT)

Replace

Failed EEV

Replace

6.12Compressor Operating in Reverse

The compressor may start in reverse for up to 10 seconds to determine correct phase rotation if required for phase detection.

Allowing the scroll compressor to operate in reverse for more than two minutes will result in internal compressor damage. Turn the start-stop switch OFF immediately.

Electrical

Incorrect wiring of compressor

Check

Incorrect wiring of compressor contactor(s)

Incorrect wiring of current sensor

6.13Abnormal Temperatures

High discharge temperature

Condenser coil dirty

7.6

Condenser fan rotating backwards

7.7

Condenser fan inoperative

7.7

Refrigerant overcharge or non-condensibles

7.3

Discharge service valve partially closed

Open

Electronic expansion valve (EEV) control malfunction

Replace

Failed suction pressure transducer (SPT),

or evaporator pressure transducer (EPT)

Replace

Discharge temperature sensor drifting high

Replace

Failed economizer expansion valve, economizer coil,

or economizer solenoid valve

Replace

Plugged economizer expansion valve, economizer coil,

or economizer solenoid valve

Replace

Loose or insufficiently clamped sensor

Replace

6.14Abnormal Currents

Unit reads abnormal currents

Current sensor wiring

Check