Section 3

DESCRIPTION

3.1General Description

3.1.1Refrigeration Unit - Front Section

The unit is designed so that the majority of the components are accessible from the front (see Figure 3.1). The unit model number, serial number and parts identification number can be found on the serial plate to the left of the receiver on the back wall of the condenser section.

3.1.2Fresh Air Makeup Vent

The function of the upper makeup air vent is to provide ventilation for commodities that require fresh air circulation. A manually operated venting system is located in the upper left access panel.

Figure 3.1  Refrigeration Unit - Front Section

Fig_rerigeration_unit_-_T359.jpg 

1.Access Panel (Evap. Fan #1)

2.Fork Lift Pockets

3.Control Box

4.Compressor Cover

5.Compressor

6.Economizer

7.Filter Drier

8.Receiver

9.Unit Serial Number, Model Number and Parts Identification Number (PID) Plate

10.Power Cables and Plug (Location)

11.Condenser Fan

12.Interrogator Connector (Front left)

13.Temperature Recorder (Provisioned)

14.TIR (Transports Internationaux Routiers) Sealing Provisions - Typical All Panels

15.Upper Fresh Air Makeup Vent Panel

16.Access Panel (Evap. Fan #2)

- - - - -

3.1.3Evaporator Section

The evaporator section (Figure 3.2) contains the return temperature sensor, humidity sensor, electronic expansion valve, dual speed evaporator fans (EM1 and EM2), evaporator coil and heaters, defrost temperature sensor, heat termination thermostat and evaporator temperature sensors (ETS1 and ETS2).

The evaporator fans circulate air through the container by pulling it in the top of the unit, directing it through the evaporator coil, where it is heated or cooled, and discharging it at the bottom.

Most evaporator components are accessible by removing the upper rear panel (as shown in the illustration) or by removing the evaporator fan access panels (see Figure 3.1, Items 1 and 16).

Figure 3.2  Evaporator Section

Fig_evap_section_-_T359.jpg 

1.Evaporator Fan Motor #1 (EM1)

2.Return Recorder Sensor/Temperature Sensor (RRS/RTS)

3.Humidity Sensor (HS)

4.Evaporator Fan Motor #2 (EM2)

5.Evaporator Coil

6.Evaporator Coil Heaters (Underside of Coil)

7.Heater Termination Thermostat (HTT)

8.Defrost Temperature Sensor (DTS)

9.Electronic Expansion Valve (EEV)

10.Evaporator Temperature Sensors (Location) (ETS1 and ETS2)

11.Interrogator Connector (Rear) (ICR)

12.USDA Probe Receptacle PR2

13.USDA Probe Receptacle PR1

14.USDA Probe Receptacle PR3

15.Cargo Probe Receptacle PR4

- - - - -

3.1.4Compressor Section

The compressor section (Figure 3.3) includes the compressor, digital unloader valve (DUV), high pressure switch, discharge pressure transducer (DPT), evaporator pressure transducer (EPT) and the suction pressure transducer (SPT).

The supply temperature sensor, supply recorder sensor and ambient sensor are located to the left of the compressor.

Figure 3.3  Compressor Section

Fig_compressor_section_-_T359.jpg 

1.Compressor

2.Compressor Discharge Temperature Sen­sor (CPDS) (Location)

3.Discharge Connection

4.Suction Connection (Location)

5.Compressor Terminal Box

6.Oil Drain (Location)

7.Economizer Connection

8.Discharge Pressure Transducer (DPT)

9.Suction Pressure Transducer (SPT)

10.Digital Unloader Valve (DUV)

11.Evaporator Pressure Transducer (EPT)

12.Discharge Service Valve

13.High Pressure Switch (HPS)

14.Suction Service Valve

15.Supply Temperature/Supply Recorder Sensor Assembly (STS/SRS)

- - - - -

3.1.5Air-Cooled Condenser Section

The air-cooled condenser section (Figure 3.4) consists of the condenser fan, condenser coil, receiver, liquid line service valve, filter drier, fusible plug, economizer, economizer expansion valve, economizer solenoid valve (ESV), and sight glass/moisture indicator.

The condenser fan pulls air through the bottom of the coil and discharges it horizontally through the con denser fan grille.

Figure 3.4  Air-Cooled Condenser Section

Fig_air-cooled_condenser_section_-_T359.jpg 

1.Grille and Venturi Assembly

2.Condenser Fan

3.Key

4.Condenser Fan Motor

5.Condenser Coil

6.Condenser Coil Cover

7.Receiver

8.Sight Glass

9.Filter Drier

10.Economizer

11.Economizer Solenoid Valve (ESV)

12.Economizer Expansion Valve

13.Service Access Valve

14.Liquid Level/Moisture Indicator

15.Fusible Plug

- - - - -

3.1.6Control Box Section

The control box (Figure 3.5) includes: the manual operation switches, circuit breaker (CB-1), compressor, fan and heater contactors, control power transformer, fuses, key pad, display module, current sensor module, controller module and the communications interface module.

3.1.7Communications Interface Module

The optional communications interface module is a slave module that allows communication with a master central monitoring station. The module will respond to communication and return information over the main power line. Refer to the master central monitoring station technical manual for additional information.

Figure 3.5  Control Box Section

Fig_control_box_section_-_T359.jpg 

1.Compressor Contactor - CH

2.Compressor Phase A Contactor - PA

3.Compressor Phase B Contactor - PB

4.Heater Contactor - HR

5.Display Module

6.Communications Interface Module

7.Controller/DataCORDER Module (Controller)

8.Key Pad

9.Remote Monitoring Receptacle

10.Controller Battery Pack (Standard Location)

11.Interrogator Connector (Box Location)

12.Control Transformer

13.Terminal Block - HW

14.High Speed Evaporator Fan Contactor - EF

15.Low Speed Evaporator Fan Contactor - ES

16.Condenser Fan Contactor - CF

17.Circuit Breaker - 460V

18.Current Sensor Module

- - - - -

3.2Refrigeration System Data

Compressor / Motor Assembly

Model Number

ZMD26KVE-TFD-274

Weight (With Oil)

42.9 kg (95 lb)

Approved Oil

Uniqema Emkarate RL-32-3MAF

Oil Charge

1774 ml (60 ounces)

Electronic Expansion Valve Superheat (Evaporator)

Verify at -18°C

(0°F) container box temperature

4.4 to 6.7°C (8 to 12°F)

Economizer Expansion Valve Super­heat

Verify at -18°C

(0°F) container box temperature

4.4 to 11.1°C (8 to 20°F)

Heater Termination Thermostat

Opens

54° (+/- 3) C = 130° (+/- 5) F

Closes

38° (+/- 4) C = 100° (+/- 7) F

High Pressure Switch

Cutout

25 (+/- 1.0) kg/cm2 = 350 (+/- 10) psig

Cut-In

18 (+/- 0.7) kg/cm2 = 250 (+/- 10) psig

Charge receiver according to nameplate specifications to ensure optimal unit performance.

Refrigerant Charge - R-134a

Receiver

4.99 kg (11 lbs)

Fusible Plug

Melting point

99°C = (210°F)

Torque

6.2 to 6.9 mkg (45 to 50 ft-lbs)

Rupture Disc

Bursts at

35 +/- 5% kg/cm2 = (500 +/- 5% psig)

Torque

6.2 to 6.9 mkg (45 to 50 ft-lbs)

Unit Weight

Refer to unit model number plate.

3.3Electrical Data

Circuit Breaker

CB-1 Trips at

29 amps

CB-2 (50 amp) Trips at

62.5 amps

CB-2 (70 amp) Trips at

87.5 amps

Compressor Motor

Full Load Amps (FLA)

13 amps @ 460 VAC

Condenser Fan Motor

 

380 VAC, Single Phase,

50 Hz

460 VAC, Single Phase,

60 Hz

Full Load Amps

1.3 amps

1.6 amps

Horsepower

0.43 hp

0.75 hp

Rotations Per Minute

1425 rpm

1725 rpm

Voltage and Frequency

360 - 460 VAC +/- 2.5 Hz

400 - 500 VAC +/- 2.5 Hz

Bearing Lubrication

Factory lubricated, additional grease not required.

Rotation

Counter-clockwise when viewed from shaft end.

Evaporator Coil Heater, Standard

Number of Heaters

4

Rating

750 watts +/- 5% @ 230 VAC

Resistance (cold)

72 ohms +/- 5%

Type

Sheath

Evaporator Coil Heater, Straight

Number of Heaters

1

Rating

750 watts +/- 7.5% @ 460 VAC

Resistance (cold)

282 ohms +/-7.5%

Type

Sheath

Drain Cup Heater, Omega

Number of Heaters

1

Rating

450 watts +5/-7.5% @ 460 VAC

Resistance (cold)

470 ohms +/-7.5%

Type

Sheath

Evaporator Fan Motor(s)

 

380 VAC/3 PH/50 Hz

460 VAC/3 PH/60 Hz

Full Load Amps

High Speed

1.0

1.2

Full Load Amps

Low Speed

0.6

0.6

Nominal Horsepower

High Speed

0.49

0.84

Nominal Horsepower

Low Speed

0.06

0.11

Rotations Per Minute

High Speed

2850 rpm

3450 rpm

Rotations Per Minute

Low Speed

1425 rpm

1725 rpm

Voltage and Frequency

360 - 460 VAC +/- 1.25 Hz

400 - 500 VAC +/- 1.5 Hz

Bearing Lubrication

Factory lubricated, additional grease not required

Fuses

Control Circuit

7.5 amps (F3A,F3B)

Controller/

DataCORDER

5 amps (F1 & F2)

Emergency Bypass

10 amps (FEB)

Vent Positioning Sensor

Electrical Output

0.5 VDC to 4.5 VDC over 90 degree range

Supply Voltage

5 VDC +/- 10%

Supply Current

5 mA (typical)

Solenoid Valve Coils (ESV) 24 VDC

Nominal Resistance @ 77°F (25°C)

7.7 ohms +/- 5%

Maximum Current Draw

0.7 amps

DUV Coils 12 VDC

Nominal Resistance @ 77°F (25°C)

14.8 ohms +/- 5%

Maximum Current Draw

929 mA

EEV Nominal Resistance

Coil Feed to Ground

(Gray Wire)

47 ohms

Coil Feed to Coil Feed

95 ohms

Humidity Sensor

Orange wire

Power

Red wire

Output

Brown wire

Ground

Input voltage

5 VDC

Output voltage

0 to 3.3 VDC

Output voltage readings verses relative humidity (RH) percentage:

30%

0.99 V

50%

1.65 V

70%

2.31 V

90%

2.97 V

Controller

Setpoint Range

-35 to +30°C (-31 to +86°F)

3.4Safety and Protective Devices

Unit components are protected from damage by safety and protective devices listed in Table 3–1. These de vices monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition occurs.

Open safety switch contacts on either or both of devices IP-CP or HPS will shut down the compressor.

Open safety switch contacts on device IP-CM will shut down the condenser fan motor.

The entire refrigeration unit will shut down if one of the following safety devices open: (a) circuit breaker(s); (b) fuse (F3A/F3B, 7.5A); or (c) evaporator fan motor internal protector(s) - (IP).

Table 3–1  Safety and Protective Devices

Unsafe Condition

Device

Device Setting

Excessive current draw

Circuit Breaker (CB-1) - Manual Reset

Trips at 29 amps (460 VAC)

Circuit Breaker (CB-2, 50 amp) - Manual Reset

Trips at 62.5 amps (230 VAC)

Circuit Breaker (CB-2, 70 amp) - Manual Reset

Trips at 87.5 amps (230 VAC)

Excessive current draw

in the control circuit

Fuse (F3A & F3B)

7.5 amp rating

Excessive current draw

by the controller

Fuse (F1 & F2)

5 amp rating

Excessive condenser fan

motor winding temperature

Internal Protector (IP-CM) - Automatic Reset

N/A

Excessive compressor

motor winding temperature

Internal Protector (IP-CP) - Automatic Reset

N/A

Excessive evaporator fan

motor(s) winding temperature

Internal Protector(s) (IP-EM) - Automatic Reset

N/A

Abnormal pressures/tempera­tures in the high refrigerant side

Fusible Plug - Used on the Receiver

99°C = (210°F)

Abnormally high

discharge pressure

High Pressure Switch (HPS)

Opens at 25 kg/cm2 

(350 psig)

3.5Refrigeration Circuit

3.5.1Standard Operation

Starting at the compressor, (see Figure 3.6) the suction gas is compressed to a higher pressure and temperature.

The refrigerant gas flows through the discharge line and continues into the air-cooled condenser. When operating with the air-cooled condenser active, air flowing across the coil fins and tubes cools the gas to saturation tempera­ture. By removing latent heat, the gas condenses to a high pressure/high temperature liquid and flows to the receiver, which stores the additional charge necessary for low temperature operation.

The liquid refrigerant continues through the liquid line, the filter drier (which keeps refrigerant clean and dry) and the economizer (not active during standard operation) to the electronic expansion valve. As the liquid refrigerant passes through the variable orifice of the expansion valve, some of it vaporizes into a gas (flash gas). Heat is absorbed from the return air by the balance of the liquid, causing it to vaporize in the evaporator coil. The vapor then flows through the suction tube back to the compressor.

During the standard mode of operation, the normally closed digital unloader valve (DUV) controls the system refrig­erant flow and capacity by loading and unloading the compressor in frequent discrete time intervals. If the system capacity has been decreased to the lowest allowable capacity with the DUV, the unit will enter a trim heat mode of operation, during which the controller will pulse the evaporator heaters in sequence with the compressor digital sig­nal in order to absorb the excess capacity.

3.5.2Economized Operation

In the economized mode, (see Figure 3.7) the frozen and pull down capacity of the unit is increased by sub cooling the liquid refrigerant entering the electronic expansion valve. Overall efficiency is increased because the gas leav­ing the economizer enters the compressor at a higher pressure, therefore requiring less energy to compress it to the required condensing conditions.

Liquid refrigerant for use in the economizer circuit is taken from the main liquid line as it leaves the filter drier. The flow is activated when the controller energizes the economizer solenoid valve (ESV).

The liquid refrigerant flows through the ESV to the expansion valve internal passages, absorbing heat from the liq­uid refrigerant flowing to the electronic expansion valve. The resultant “medium” temperature/pressure gas enters the compressor at the economizer port fit ting.

When the air temperature falls to 2.0°C (3.6°F) above set point, the DUV unloads the compressor's scroll and begins to reduce the capacity of the unit. Percentage of the unit capacity is accessed through code select 01 (Cd01). For example, if Cd01 displays 70, it indicates that the compressor is operating unloaded with the DUV engaged 30% of the time.

3.5.3Electronic Expansion Valve

The microprocessor controls the superheat leaving the evaporator via the electronic expansion valve (EEV), based on inputs from the evaporator pressure transducer (EPT). The microprocessor transmits electronic pulses to the EEV stepper motor, which opens or closes the valve orifice to maintain the superheat set point.

Figure 3.6  Refrigeration Circuit Schematic - Standard Operation

Fig_rerigeration_circuit_schematic_standard_-_T359.jpg 

Figure 3.7  Refrigeration Circuit Schematic - Economized Operation

Fig_rerigeration_circuit_schematic_economized_-_T359.jpg