Section 4

MICROPROCESSOR

4.1Temperature Control Microprocessor System

The temperature control Micro-Link 3 microprocessor system (see Figure 4.1) consists of a keypad, display mod­ule, the control module (controller) and interconnecting wiring. The controller houses the temperature control soft­ware and the DataCORDER software. The temperature control software functions to operate the unit components as required to provide the desired car go temperature and humidity. The DataCORDER soft ware functions to record unit operating parameters and cargo temperature parameters for future retrieval. Cover age of the tempera­ture control software begins with Section 4.2. Coverage of the DataCORDER software is provided in Section 4.7.

The keypad and display module serve to provide user access and readouts for both of the controller functions, tem­perature control and DataCORDER. The functions are accessed by keypad selections and viewed on the display module. The components are designed to permit ease of installation and removal.

Figure 4.1  Temperature Control System

fig178_mv.jpg 

4.1.1Keypad

Figure 4.2  Keypad

fig12_mv.jpg 

Table 4–1  Keypad Function

Key

Function

CODE

SELECT

Accesses function codes.

PRE TRIP

Displays Pre-trip selection menu.

Discontinues Pre-trip in progress.

ALARM LIST

Displays alarm list and clears the

alarm queue.

MANUAL

DEFROST /

INTERVAL

Displays selected defrost mode.

Depress and hold the MANUAL DEFROST / INTERVAL key for five (5) seconds to initiate defrost using the same logic as if the optional manual defrost switch was toggled on.

ENTER

Confirms a selection or saves a selection to the controller.

Arrow Up

Change or scroll a selection up. Pre-trip advance or test interrupt.

Arrow Down

Change or scroll selection downward. Pre-trip repeat backward.

RETURN /

SUPPLY

Display non-controlling probe temperature (momentary display).

Celsius /

Fahrenheit

Display alternate English / Metric scale (momentary display). When set to F, pressure is displayed in psig and vacuum in “/hg.” “P” appears after the value to indicate psig and “i” appears for inches of mercury. When set to C, pressure readings are in bars. “b” appears after the value to indicate bars.

BATTERY

POWER

Initiate battery backup mode to allow set point & function code selection if AC power is not connected.

ALT MODE

This key is pressed to switch the functions from temperature software to the DataCORDER software. The remaining keys function the same as described above except the readings or changes are made to the DataCORDER programming.

 

4.1.2Display Module

The display module (Figure 4.3) consists of two 5-digit displays and seven indicator lights. The indicator lights include:

1.Cool - White or Blue LED: Energized when the refrigerant compressor is energized.

2.Heat - Orange LED: Energized to indicate heater operation in the heat or defrost mode.

3.Defrost - Orange LED: Energized when the unit is in the defrost mode.

4.In-Range - Green LED: Energized when the controlled temperature probe is within specified tolerance of set point.

The controlling probe in the perishable range will be the SUPPLY air probe and the controlling probe in the frozen range will be the RETURN air probe.

5.Supply - Yellow LED: Energized when the supply air probe is used for control. When this LED is illuminated, the temperature displayed in the AIR TEMPERATURE display is the reading at the supply air probe. This LED will flash if dehumidification or humidification is enabled.

6.Return - Yellow LED: Energized when the return air probe is used for control. When this LED is illuminated, the temperature displayed in the AIR TEMPERATURE display is the reading at the return air probe. This LED will flash if dehumidification or humidification is enabled.

7.Alarm - Red LED: Energized when there is an active or an inactive shutdown alarm in the alarm queue.

Figure 4.3  Display Module

Fig_display_module_T-359.jpg 

4.1.3Controller

Do not remove wire harnesses from circuit boards unless you are grounded to the unit frame with a static safe wrist strap or equivalent static drain device.

Remove the controller module and unplug all connectors before performing any arc welding on any part of the container.

Do not attempt to use an ML2i PC card in an ML3 equipped unit. The PC cards are physically different and will result in damage to the controller.

Do not attempt to service controller modules. Breaking the seal will void the warranty.

The Micro-Link 3 controller is a dual module microprocessor as shown in Figure 4.4. It is fitted with test points, har­ness connectors and a software card programming port.

Figure 4.4  Control Module

Fig_control_module_-_T359.jpg 

1.Mounting Screw

2.Micro-Link 3 Control/DataCORDER Module

3.Connectors

4.Test Points

5.Fuses

6.Control Circuit Power Connection

7.Software Programming Port

8.Battery Pack (Standard Location)

- - - - -

4.2Controller Software

The controller software is a custom designed program that is subdivided into configuration software and opera­tional software. The controller software performs the fol lowing functions:

a.Control supply or return air temperature to required limits, provide modulated refrigeration operation, econo­mized operation, unloaded operation, electric heat control and defrost. Defrost is performed to clear buildup of frost and ice and ensure proper air flow across the coil.

b.Provide default independent readouts of set point and supply or return air temperatures.

c.Provide ability to read and (if applicable) modify the configuration software variables, operating software Function Codes and Alarm Code indications.

d.Provide a Pre-trip step-by-step checkout of refrigeration unit performance including: proper component operation, electronic and refrigeration control operation, heater operation, probe calibration, pressure limit­ing and current limiting settings.

e.Provide battery-powered ability to access or change selected codes and set point without AC power connected.

f.Provide the ability to reprogram the software through the use of a memory card.

4.2.1Configuration Software (Variables)

The configuration software is a variable listing of the components available for use by the operational soft ware. This software is factory installed in accordance with the equipment fitted and options listed on the original purchase order. Changes to the configuration soft ware are required only when a new controller has been installed or a phys­ical change has been made to the unit such as the addition or removal of an option. A configuration variable list is provided in Table 4–4. Change to the factory-installed configuration software is achieved via a configuration card or by communications.

4.2.2Operational Software (Function Codes)

The operational software is the actual operation programming of the controller which activates or deactivates com­ponents in accordance with current unit operating conditions and operator selected modes of operation.

The programming is divided into function codes. Some of the codes are read only while the remaining codes may be user configured. The value of the user configurable codes can be assigned in accordance with user desired mode of operation. A list of the function codes is provided in Table 4–5.

To access the function codes, perform the following:

a.Press the CODE SELECT key, then press an arrow key until the left window displays the desired code number.

b.The right window will display the value of this item for five seconds before returning to the normal display mode.

c.If a longer time is desired, press the ENTER key to extend the time to five minutes.

4.3Controller Sequence and Modes of Operation

General operation sequences for cooling, heating, and defrost are provided in the following sub-paragraphs. Sche­matic representation of controller action is provided in Figure 4.5.

The operational software responds to various inputs. These inputs come from the temperature and pressure sensors, the temperature set point, the settings of the configuration variables and the function code assignments. The action taken by the operational software will change if any one of the inputs change. Overall interaction of the inputs is described as a “mode” of operation. The modes of operation include perishable (chill) mode and frozen mode. Descriptions of the controller interaction and modes of operation are provided in the following sub paragraphs.

4.3.1Start Up - Compressor Phase Sequence

The controller logic will check for proper phase sequencing and compressor rotation. If sequencing is allowing the compressor and three-phase evaporator fan motor to rotate in the wrong direction, the controller will energize or de-energize relay TCP as required (see Figure 8.2). Relay TCP will switch its contacts, energizing or de-energizing relays PA and PB. Relay PA is wired to energize the circuits(s) on L1, L2, and L3. Relay PB is wired to energize the circuit(s) on L3, L2, and L1, thus providing reverse rotation.

4.3.2Start Up - Compressor Bump Start

The controller logic will initiate a compressor bump start procedure to clear refrigerant from the compressor. If suc­tion and discharge pressures have equalized, the compressor will perform three compressor bump starts. A com­pressor bump start may occur after a defrost has been completed.

During the procedure, the EEV will close. Relays TS, TQ, TN, TE, TV will be de-energized (opened). The result of this action will close the ESV and shut all fans off. The compressor will start for 1 second, then pause for five sec­onds. This sequence will be repeated two additional times. After the final bump start the unit will pre-position the EEV to correct starting position pause and startup.

4.3.3Perishable Set Point Temperature - Perishable Pulldown

When cooling from a temperature that is more than 2.5°C (4.5°F) above set point, the system will be in the perish­able pulldown mode in economized operation. However, pressure and current limit functions may restrict the valve if either exceeds the preset value.

4.3.4Perishable Set Point Temperature - Standard Temperature Control Mode

The unit is capable of maintaining supply air temperature to within +/-0.2°C (+/-0.36°F) of set point. Supply air tem­perature is controlled by positioning of the electronic expansion valve (EEV), cycling of the digital unloader valve (DUV), cycling of the compressor and cycling of the heaters.

Once set point is reached, the unit will transition to the perishable steady state mode. This results in unloaded operation by cycling the DUV to limit capacity and maintain steady temperature control.

If the controller has determined that cooling is not required or the controller logic determines suction pressure is at the low pressure limit, the unit will transition to the perishable idle mode. The compressor is turned off and the evaporator fans continue to run to circulate air throughout the container. If temperature rises above set point +0.2°C, the unit will transition back to the perish able steady state mode

If the temperature drops to 0.5°C (0.9°F) below set point, the unit will transition to the perishable heating mode and the heaters will be energized. The unit will transition back to the perishable idle mode when the temperature rises to 0.2°C (0.4°F) below the set point and the heaters will de-energize.

4.3.5Perishable Set Point Temperature - Economy Fan Operation Mode

The economy mode is an extension of the standard mode. The mode is activated when the setting of function code Cd34 is “ON”. Economy mode is provided for power saving purposes. Economy mode could be utilized in the transportation of temperature-tolerant cargo or non-respiration items which do not require high air flow for removing respiration heat. There is no active display indicator that economy mode has been activated. To check for economy mode, perform a manual display of code Cd34.

In order to achieve economy mode, a perishable set point must be selected prior to activation. When economy mode is active, the evaporator fans will be controlled as follows:

At the start of each cooling or heating cycle, the evaporator fans will run in high speed for three minutes. They will then be switched to low speed any time the supply air temperature is within +/- 0.2°C (0.36°F) of the set point and the return air temperature is less than or equal to the supply air temperature +3°C (5.4°F). The fans will continue to run in low speed for one hour. At the end of the hour, the evaporator fans will switch back to high speed and the cycle will be repeated. If bulb mode is active, the economy fan activity will be overridden.

4.3.6Perishable Set Point Temperature Control

With configuration variable CnF26 (Heat Lockout Temperature) set to -10°C the perishable mode of operation is active with set points above -10°C (+14°F). With the variable set to -5°C, the perishable mode is active above -5°C (+23°F). Refer to Table 4–4.

When in the perishable mode, the controller maintains the supply air temperature at set point, the SUPPLY indica­tor light will be illuminated on the display module and the default reading on the display window will be the supply temperature sensor reading.

When the supply air temperature enters the in-range temperature tolerance (as selected at function code Cd30), the in-range light will energize.

Figure 4.5  Controller Operation - Perishable Mode

Fig_controller_operation_perishable_T-359.jpg 

4.3.7Perishable Mode Cooling - Sequence of Operation

In the Standard Perishable Mode of Operation, the evaporator motors run in high speed. In the Econ­omy Perishable Mode, the fan speed is varied.

With supply air temperature above set point and decreasing, the unit will cool with the condenser fan motor (CF), compressor motor (CH), evaporator fan motors (EF) energized and the COOL light illuminated. (See Figure 4.6). Also, if current or pressure limiting is not active, the controller may close contacts TS to open the economizer sole­noid valve (ESV) and place the unit in economized operation.

When the air temperature decreases to a predetermined tolerance above set point, the in-range light is illuminated.

Figure 4.6  Perishable Mode - Cooling

Fig_perishable_mode_cooling__T-359.jpg 

4.3.8Perishable Mode Heating - Sequence of Operation

a.If the air temperature decreases 0.5°C (0.9°F) below set point, the system enters the heating mode. (See Figure 4.5). The controller closes contacts TH (see Figure 4.7) to allow power flow through the heat termi­nation thermostat (HTT) to energize the heaters (HR). The HEAT light is also illuminated. The evaporator fans continue to run to circulate air throughout the container.

b.When the temperature rises to 0.2°C (0.4°F) below set point, contacts TH open to de-energize the heaters. The HEAT light is also de-energized. The evaporator fans continue to run to circulate air throughout the container.

c.The safety heater termination thermostat (HTT) is attached to an evaporator coil circuit and will open the heating circuit if overheating occurs.

Figure 4.7  Perishable Mode Heating

Fig_perishable_mode_heating__T-359.jpg

4.3.9Sequence of Operation - Perishable Mode (Capacity Trim Heat)

If the system capacity has been decreased to the lowest allowable capacity and conditions exist that warrant max­imum temperature stability the controller will pulse the HR relay to energize the evaporator heaters in sequence with the compressor digital signal. Trim heat is enabled only if (12.77°C < set point < 15.55°C [54.99°F < set point < 59.99°F]) and (-6.67°C < ambient temperature < 1.66°C [19.99°F < ambient temperature < 34.99°F]).

4.3.10Perishable Mode - Dehumidification

The dehumidification mode is provided to reduce the humidity levels inside the container. The mode is activated when a humidity value is set at function code Cd33. The display module SUPPLY LED will flash ON and OFF every second to indicate that the dehumidification mode is active. Once the Mode is active and the following conditions are satisfied, the controller will activate the heat relay to begin dehumidification.

1.The humidity sensor reading is above the set point.

2.The unit is in the perishable steady state mode and supply air temperature is less than 0.25°C (0.38°F) above set point.

3.The heater debounce timer (three minutes) has timed out.

4.Heater termination thermostat (HTT) is closed.

If the above conditions are true the evaporator fans will switch from high to low speed operation. The evaporator fan speed will switch every hour thereafter as long as all conditions are met (see Bulb Mode section for different evaporator fan speed options). If any condition except item (1) becomes false OR if the relative humidity sensed is 2% below the dehumidification set point, the high speed evaporator fans will be energized.

Power is applied to the defrost heaters in the dehumidification mode. This added heat load causes the controller to open the ESV to match the increased heat load while still holding the supply air temperature very close to the set point.

Opening the ESV reduces the temperature of the evaporator coil surface, which increases the rate at which water is condensed from the passing air. Removing water from the air reduces the relative humidity. When the relative humidity sensed is 2% below the set point, the controller de-energizes the heat relay. The controller will continue to cycle heating to maintain relative humidity below the selected set point. If the mode is terminated by a condition other than the humidity sensor, e.g., an out-of-range or compressor shutdown condition, the heat relay is de-ener­gized immediately.

Two timers are activated in the dehumidification mode to prevent rapid cycling and consequent contactor wear. They are:

1.Heater debounce timer (three minutes).

2.Out-of-range timer (five minutes).

The heater debounce timer is started whenever the heater contactor status is changed. The heat contactor remains energized (or de-energized) for at least three minutes even if the set point criteria are satisfied.

The out-of-range timer is started to maintain heater operation during a temporary out-of-range condition. If the sup­ply air temperature remains outside of the user selected in-range setting for more than five minutes, the heaters will be de-energized to allow the system to recover. The out-of-range timer starts as soon as the temperature exceeds the in-range tolerance value set by function code Cd30.

4.3.11Perishable, Dehumidification - Bulb Mode

Bulb mode is an extension of the dehumidification mode, which allows changes to the evaporator fan speed and/or defrost termination set points.

Bulb mode is active when configuration code Cd35 is set to “Bulb”. Once the bulb mode is activated, the user may then change the dehumidification mode evaporator fan operation from the default (speed alternates from low to high each hour) to constant low or constant high speed. This is done by toggling function code Cd36 from its default of “alt” to “Lo” or “Hi” as desired. If low speed evaporator fan operation is selected, this gives the user the additional capability of selecting dehumidification set points from 60 to 95% (instead of the normal 65 to 95%).

In addition, if bulb mode is active, function code Cd37 may be set to override the previous defrost termination thermo­stat settings. (Refer to Section 4.3.18) The temperature at which the defrost termination thermostat will be consid­ered “open” may be changed [in 0.1°C (0.2°F) increments] to any value between 25.6°C (78°F) and 4°C (39.2°F). The temperature at which the defrost termination thermostat is considered closed for interval timer start or demand defrost is 10°C for “open” values from 25.6°C (78°F) down to a 10°C setting. For “open” values lower than 10°C, the “closed” values will decrease to the same value as the “open” setting. Bulb mode is terminated when:

1.Bulb mode code Cd35 is set to “Nor”.

2.Dehumidification code Cd33 is set to “Off”.

3.The user changes the set point to one that is in the frozen range.

When bulb mode is disabled by any of the above, the evaporator fan operation for dehumidification reverts to “alt” and the DTS termination setting resets to the value determined by controller configuration variable CnF41.

4.3.12Frozen Mode - Temperature Control

When in the frozen mode, the controller maintains the return air temperature at or below set point, the RETURN indicator light will be illuminated on the display module and the default reading on the display window will be the return air probe reading.

When the return air temperature enters the in-range temperature tolerance as selected at function code Cd30, the in-range light will energize.

Figure 4.8  Controller Operation - Frozen Mode

Fig_controller_operation_frozen_T-359.jpg 

4.3.13Frozen Mode - Standard

Frozen range cargos are not sensitive to minor temperature changes. The method of temperature control employed in this range takes advantage of this to greatly improve the energy efficiency of the unit. Temperature control in the frozen range is accomplished by cycling the compressor on and off as the load demand requires.

When temperature drops to set point minus 0.2°C and the compressor has run for at least five minutes, the unit will transition to the frozen idle mode. The compressor is turned off and the evaporator fans continue to run to circulate air throughout the container. If temperature rises above set point +0.2°C, the unit will transition back to the frozen mode cooling.

4.3.14Frozen Mode - Heat Lockout Temperature

With configuration variable CnF26 (Heat Lockout Temperature) set to -10°C the frozen mode of operation is active with set points at or below -10°C (+14°F). With the variable set to -5°C, the frozen mode is active at or below -5°C (+23°F).

If the temperature drops 10°C below set point, the unit will transition to the frozen “heating” mode, in which the evaporator fans are brought to high speed. The unit will transition back to the frozen mode cooling when the tem­perature rises back to the transition point.

4.3.15Frozen Mode Cooling - Sequence of Operation

a.When the return air temperature is above set point and decreasing, the unit will transition to economized cooling with the condenser fan motor (CF), compressor motor (CH), economizer solenoid valve (ESV), low speed evaporator fan motors (ES) energized and the COOL light illuminated. (See Figure 4.9).

b.When the air temperature decreases to a predetermined tolerance above set point, the in-range light is illu­minated.

c.When the return air temperature decreases to 0.2°C (0.4°F) below set point, contacts TC, TS, and TN are opened to de-energize the compressor, economizer solenoid valve and condenser fan motor. The cool light is also de-energized. The EEV will close.

d.The evaporator fan motors continue to run in low speed to circulate air throughout the container. The in-range light remains illuminated as long as the return air is within tolerance of set point.

e.If return air temperature drops to 10°C (18°F) or more below set point, the evaporator fans increase to high speed.

f.When the return air temperature increases to 0.2°C (0.4°F) above set point and three minutes have elapsed, the EEV opens and contacts TC, TS and TN close to restart the compressor, open the ESV and restart the condenser fan motor. The cool light is illuminated.

Figure 4.9  Frozen Mode

Fig_frozen_mode_T-359.jpg 

The EEV and DUV are independently operated by the microprocessor. For full diagrams and legend, see Section 8.

4.3.16Frozen Mode - Economy

In order to activate economy frozen mode operation, a frozen set point temperature must be selected. The economy mode is active when function code Cd34 is set to “ON”. When economy mode frozen is active, the system will per­form normal frozen mode operations except that the entire refrigeration system, excluding the controller, will be turned off when the control temperature is less than or equal to the set point -2°C. After an off-cycle period of 60 min­utes, the unit will turn on high speed evaporator fans for three minutes, and then check the control temperature. If the control temperature is greater than or equal to the set point +0.2°C, the unit will restart the refrigeration system and continue to cool until the previously mentioned off-cycle temperature criteria are met. If the control temperature is less than the set point +0.2°C, the unit will turn off the evaporator fans and restart another 60 minute off-cycle.

4.3.17Defrost Interval

Controller function code Cd27 sets two modes for defrost initiation, either user-selected timed intervals or auto­matic control. The user-selected values are 3, 6, 9, 12, 24 hours, AUTO, or PuLs. Some units may be configured to allow defrost to be disabled altogether. In this case, a user-selected value of OFF will be available. The factory default for defrost is AUTO. Refer to Table 4–5.

In perishable mode, perishable-pulldown mode, or frozen-pulldown mode, automatic defrost starts with an initial defrost set to three hours and then adjusts the interval to the next defrost based on the accumulation of ice on the evaporator coil. In this way, defrosts are scheduled to occur only when necessary.

Once set point has been reached in frozen operation, the automatic selection will set the time interval to 12 hours for the first two defrosts once the return probe is reading below the frozen set point and then adjust to 24 hours thereafter.

All defrost interval times reflect the number of compressor runtime hours since the last defrost de-ice cycle. The minimum defrost interval under the automatic setting is three hours while the maximum is 24. In frozen mode the amount of wall-clock time necessary to accumulate a given amount of defrost interval time will exceed the defrost interval time by a factor of two to three depending on the compressor duty-cycle. Defrost inter val time is not accu­mulated in any mode until the defrost termination sensor reads less than 10°C (50°F).

If defrost does not terminate correctly and temperature reaches set point of the heat termination thermostat (HTT), the thermostat will open to de-energize the heaters. If termination does not occur within two hours, the controller will terminate defrost. An alarm will be activated to inform of a possible DTS failure.

If probe check (controller function code CnF31) is con figured to SPECIAL, the unit will proceed to the next opera­tion (snap freeze or terminate defrost). If the code is configured to STANDARD, the unit will perform a probe check. The purpose of the probe check is to detect malfunctions in the sensed temperature. If probe check fails, the sys­tem will run for eight minutes to validate. At the end of eight minutes, probe alarms will be set or cleared based on the conditions seen.

When the return air falls to 7°C (45°F), the controller ensures that the defrost temperature sensor (DTS) reading has dropped to 10°C or below. If it has not, a DTS failure alarm is given and the defrost mode is operated by the return temperature sensor (RTS).

If controller function code CnF33 is configured to snap freeze, the controller will sequence to this operation. The snap freeze consists of running the compressor without the evaporator fans in operation for a period of 4 minutes at 100% capacity. When the snap freeze is completed, defrost is formally terminated.

4.3.18Defrost Mode - Sequence of Operation

The defrost cycle may consist of up to three distinct operations. The first is de-icing of the coil, the second is a probe check cycle and the third is snap freeze. Defrost may be initiated by any one of the following methods:

1.The manual defrost function (also manual defrost switch function, if equipped) is initiated by the user through the use of the keypad or manual defrost switch. The manual defrost function is ended by use of the DTS.

The Manual Defrost / Interval key can be used to initiate a manual defrost.

Manual Defrost/Interval key operation:

Depressing and holding the Manual Defrost / Interval key for five seconds will initiate defrost. If the Man­ual Defrost / Interval key is released in less than five seconds, defrost interval (code 27) shall be dis­played.

2.The user sends a defrost command by communications.

3.The defrost interval timer (controller function code Cd27) reaches the defrost interval set by the user.

4.The controller probe diagnostic logic determines that a probe check is necessary based on the temperature values currently reported by the supply and return probes.

5.If the controller is programmed with the Demand Defrost option and the option is set to “IN” the unit will enter defrost if it has been in operation for more than 2.5 hours without reaching set point.

6.The system is actively in a compressor suction pressure or high pressure ratio protection mode and reduced the average system capacity below a predetermined threshold value.

Defrost may be initiated any time the defrost temperature sensor reading falls below the controller defrost termina­mion thermostat set point. Defrost will terminate when the defrost temperature sensor reading rises above the defrost termination thermostat set point. The defrost termination thermostat is not a physical component. It is a controller set­ting that acts as a thermo stat, “closing” (allowing defrost) when the defrost temperature sensor reading is below the set point and “opening” (terminating or preventing defrost) when the sensor temperature reading is above set point. When the unit is operating in bulb mode (refer to Section 4.3.11), special settings may be applicable.

If the controller is programmed with the Lower DTT set ting option, the defrost termination thermostat set point may be configured to the default of 25.6°C (78°F) or lowered to 18°C (64°F). When a request for defrost is made through the manual defrost switch, communications or probe check the unit will enter defrost if the de frost tem­perature thermostat reading is at or below the defrost termination thermostat setting. Defrost will terminate when the defrost temperature sensor reading rises above the defrost termination thermostat setting. When a request for defrost is made with the defrost interval timer or by demand defrost, the defrost temperature setting must be below 10°C (50°F).

When the defrost mode is initiated, the controller closes the EEV, opens contacts TC, TN, and TE (or TV) to de-energize the compressor, condenser fan and evaporator fans. The COOL light is also de-energized. The controller then closes contacts TH to supply power to the heaters. The defrost light is illuminated. When the defrost tempera­ture sensor reading rises to the defrost termination thermostat setting, the de-icing operation is terminated.

Figure 4.10  Defrost

fig_defrost_T359.jpg 

The EEV and DUV are independently operated by the microprocessor. For full diagrams and legend, see Section 8.

4.3.19Defrost Pulsing

Pulse defrost logic periodically turns on the evaporator fans to circulate warm air around the drain line system, this prevents water re-freezing during a defrost cycle.

To enable Defrost Pulsing, the user will scroll to Function Code 27, select “PuLs” and press the Enter key. Once “PuLs” has been selected the user will then scroll to Function Code 60 and select the “Pulse Logic Set Point Engagement Temperature”. The selections are from 0.0°C (32°F) to -18°C (0°F). At the selected Engagement set point or below, “PuLs” will be active, and the evaporator fans may turn on. At set points above the selected Engagement set point, “AUTO” defrost will be active.

Default setting for “PuLs” is -18°C (0°F). The unit will reset to the default setting at the next PTI or Trip Start.

The default defrost interval for “PuLs” will be every 6 hours. Defrost termination setting for “PuLs” is set to 20°C (68°F).

During defrost the evaporator fans will cycle ON Low Speed once DTS reaches 0°C (32°F) and STS is below -5°C (23°F). Once the evaporator fans cycle ON the controller will monitor STS at 1 second intervals and calculate the difference between the current STS reading and the previous STS reading.

If STS becomes warmer that -5°C (23°F) or the calculated difference of STS remains below 0.1°C (0.18°F) for 10 consecutive readings or DTS reaches 20°C (68°F), the evaporator fans will turn off for 3 minutes. At the end of 3 minutes, the controller will begin checking the conditions for evaporator fans “PuLs” operation again.

4.4Protection Modes of Operation

4.4.1Evaporator Fan Operation

Opening of an evaporator fan internal protector will shut down the unit.

4.4.2Failure Action

Function code Cd29 may be operator set to select action the controller will take upon system failure. The factory default is full system shutdown. Refer to Table 4–5.

4.4.3Generator Protection

Function codes Cd31(Stagger Start, Offset Time) and Cd32 (Current Limit) may be operator set to control start up sequence of multiple units and operating current draw. The factory default allows on demand starting (no delay) of units and normal current draw. Refer to Table 4–5.

4.4.4Compressor High Temperature, Low Pressure Protection

The controller monitors compressor discharge pres sure, and temperature and suction pressure. If dis charge pres­sure or temperature rises above the allowed limit or suction pressure falls below the allowed limit, the compressor will be cycled off and on every 3 minutes. Condenser and evaporator fans continue to operate during the compres­sor off cycle.

If high compressor dome temperature occurs, the controller will allow additional refrigerant to be released into the system in order to provide cooling to the evaporator coil and compressor dome. The controller is alerted to high compressor dome temperatures via the CPDS when the ambient temperature is greater than 43.3°C, the return air temperature is less than -17.5°C and if the compressor discharge temperature is greater than 117.7°C.

Dome temperature control logic will disengage when return air temperature and ambient temperature return to allowed limits or when compressor turns off.

If the suction pressure low limit is triggered, the DUV will energize to raise the suction pressure.

4.4.5Perishable Mode - System Pressure Regulation

In perishable mode, system pressures may need to be regulated at ambient temperatures of 20°C (68°F) and below. Once below this ambient temperature, the con denser fan may cycle on and off based on limits imposed for discharge pressure. For extremely cold ambient temperatures, -18°C (0°F), heater cycling may occur within normal system operation based on discharge pressure limits.

4.4.6Condenser Fan Override

When configuration variable CnF17 (Discharge Temperature Sensor) is set to “In” and CnF48 (Condenser Fan Switch Override) is set to “On”, the condenser fan switch override logic is activated. If condenser cooling water pressure is sufficient to open the water pressure switch (de-energizing the condenser fan) when water flow or pres­sure conditions are not maintaining dis charge temperature, the logic will energize the condenser fan as follows:

1.If the DUV is less than 80% open when the controller calls for it to be100% open, the condenser fan is ener­gized. When the DUV is 100% open, the fan will de-energize.

2.If DPT reading is invalid or out of range (AL 65), the condenser fan is energized and will remain energized until system power is cycled.

3.If the system is running on condenser fan override and the high pressure switch opens, the condenser fan is energized and will remain energized until the system power is cycled.

4.5Controller Alarms

Alarm display is an independent controller software function. If an operating parameter is outside of expected range or a component does not return the correct signals back to the controller, an alarm is generated. A listing of the alarms is provided in Table 4–6.

The alarm philosophy balances the protection of the refrigeration unit and that of the refrigerated cargo. The action taken when an error is detected always considers the survival of the cargo. Rechecks are made to confirm that an error actually exists.

Some alarms requiring compressor shutdown have time delays before and after to try to keep the compressor on line. An example is alarm code “LO”, (low main voltage), when a voltage drop of over 25% occurs, an indication is given on the display, but the unit will continue to run.

When an Alarm Occurs:

a.The red alarm light will illuminate for alarm code numbers 15, 17, 20, 21, 22, 23, 24, 25, 26, and 27.

b.If a detectable problem exists, its alarm code will be alternately displayed with the set point on the left display.

c.The user should scroll through the alarm list to deter mine what alarms exist or have existed. Alarms must be diagnosed and corrected before Alarm List can be cleared.

To Display Alarm Codes:

a.While in the Default Display mode, press the ALARM LIST key. This accesses the Alarm List Display Mode, which displays any alarms archived in the alarm queue.

b.The alarm queue stores up to 16 alarms in the sequence in which they occurred. The user may scroll through the list by depressing an ARROW key.

c.The left display will show “AL##”, where ## is the alarm number sequentially in the queue.

d.The right display will show the actual alarm code. “AA##” will display for an active alarm, where “##” is the alarm code. Or “IA##” will display for an inactive alarm, See Table 4–6.

e.“END” is displayed to indicate the end of the alarm list if any alarms are active.

f.“CLEAr” is displayed if all alarms are inactive. The alarm queue may then be cleared by pressing the ENTER key. The alarm list will clear and “-----” will be displayed.

AL26 is active when all of the sensors are not responding. Check the connector at the back of the con­troller; if it is loose or unplugged, reconnect it, then run a pre-trip test (P5) to clear AL26.

4.6Unit Pre-Trip Diagnostics

Pre-trip Diagnostics is an independent controller function that suspends normal refrigeration controller activities and provides preprogrammed test routines. The test routines include Auto Mode testing, which automatically pre­forms a pre-programmed sequence of tests, or Manual Mode testing, which allows the operator to select and run any of the individual tests.

Pre-trip inspection should not be per formed with critical temperature cargoes in the container.

When Pre-trip key is pressed, economy, de humidification and bulb mode will be deactivated. At the completion of Pre-trip activity, economy, dehumidification and bulb mode must be reactivated.

Testing may be initiated by use of the keypad or via communication, but when initiated by communication the con­troller will execute the entire battery of tests (auto mode).

At the end of a pre-trip test, the message “P,” “rSLts” (pretest results) will be displayed. Pressing the ENTER key will allow the user to see the results for all subtests. The results will be displayed as “PASS” or “FAIL” for all the tests run to completion.

A detailed description of the pre-trip tests and test codes is provided in Table 4–7. Detailed operating instructions are provided in Section 5.7.

4.7DataCORDER

4.7.1Description

The Carrier Transicold “DataCORDER” software is integrated into the controller and serves to eliminate the tem­perature recorder and paper chart. The DataCORDER functions may be accessed by keypad selections and viewed on the display module. The unit is also fitted with interrogation connections (see Figure 4.1) which may be used with the Carrier Transicold Data Reader to download data. A personal computer with Carrier Transicold DataLINE software may also be used to download data and configure settings. The DataCORDER consists of:

Configuration Software

Operational Software

Data Storage Memory

Real Time Clock (with internal battery backup)

Six Thermistor Inputs

Interrogation Connections

Power Supply (battery pack)

The DataCORDER performs the following functions:

a.Logs data at 15, 30, 60, or 120 minute intervals and stores two years of data (based on one-hour interval).

b.Records and displays alarms on the display module.

c.Records results of pre-trip testing.

d.Records DataCORDER and temperature control software generated data and events as follows:

Container ID Change

Software Upgrades

Alarm Activity

Battery Low (battery pack)

Data Retrieval

Defrost Start and End

Dehumidification Start and End

Power Loss (with and without battery pack)

Power Up (with and without battery pack)

Remote Probe Temperatures in the Con­tainer (USDA Cold treatment and Cargo probe recording)

Return Air Temperature

Set Point Change

Supply Air Temperature

Real Time Clock Battery (internal battery) Replacement

Real Time Clock Modification

Trip Start

ISO Trip Header (When entered via Interro­gation program)

Economy Mode Start and End

“Auto 1/Auto 2/Auto 3" Pre-trip Start and End

Bulb Mode Start

Bulb Mode Changes

Bulb Mode End

USDA Trip Comment

Humidification Start and End

USDA Probe Calibration

Fresh Air Vent Position

- - - - -

4.7.2DataCORDER Software

The DataCORDER Software is subdivided into the Operational Software, Configuration Software, and the Data Memory.

a.Operational Software

The Operational Software reads and interprets inputs for use by the Configuration Software. The inputs are labeled Function Codes. Controller functions (see Table 4–8) which the operator may access to examine the current input data or stored data. To access these codes, do the following:

1.Press the ALT. MODE and CODE SELECT keys.

2.Press an arrow key until the left window displays the desired code number. The right window will display the value of this item for five seconds before returning to the normal display mode.

3.If a longer display time is desired, press the ENTER key to extend the display time to five minutes.

b.Configuration Software

The configuration software controls the recording and alarm functions of the DataCORDER. Reprogramming to the factory-installed configuration is achieved via a configuration card. Changes to the unit DataCORDER configuration may be made using the DataLINE interrogation software. A listing of the configuration variables is provided in Table 4–2. Descriptions of Data CORDER operation for each variable setting are provided in the following paragraphs.

4.7.3Sensor Configuration (dCF02)

Two modes of operation may be configured, the Standard Mode and the Generic Mode.

a.Standard Mode

In the standard mode, the user may configure the DataCORDER to record data using one of seven standard con­figurations. The seven standard configuration variables, with their descriptions, are listed in Table 4–3.

The inputs of the six thermistors (supply, return, USDA #1, #2, #3, and cargo probe) and the humidity sensor input will be generated by the DataCORDER. See Figure 4.11.

The DataCORDER software uses the supply and return recorder sensors (SRS, RRS). The tempera­ture control software uses the supply and return temperature sensors (STS, RTS).

b.Generic Mode

The generic recording mode allows user selection of the network data points to be recorded. The user may select up to a total of eight data points for recording. A list of the data points available for recording follows. Changing the configuration to generic and selecting which data points to record may be done using the Carrier Transicold Data Retrieval Program.

1.Control mode

2.Control temperature

3.Frequency

4.Humidity

5.Phase A current

6.Phase B current

7.Phase C current

8.Main voltage

9.Evaporator expansion valve percentage

10.Discrete outputs (Bit mapped - require special handling if used)

11.Discrete inputs (Bit mapped - require special handling if used)

12.Ambient sensor

13.Evaporator temperature sensor

14.Compressor discharge sensor

15.Return temperature sensor (RTS)

16.Supply temperature sensor (STS)

17.Defrost temperature sensor

18.Discharge pressure transducer

19.Suction pressure transducer

20.Condenser pressure transducer

21.Vent position sensor (VPS)

- - - - -

4.7.4Logging Interval (dCF03)

The user may select four different time intervals between data recordings. Data is logged at exact intervals in accordance with the real time clock. The clock is factory set at Greenwich Mean Time (GMT).

4.7.5Thermistor Format (dCF04)

The user may configure the format in which the thermistor readings are recorded. The short resolution is a 1 byte format and the long resolution is a 2 byte format. The short requires less memory and records temperature with variable resolutions depending on temperature range. The long records temperature in 0.01°C (0.02°F) steps for the entire range.

Table 4–2  DataCORDER Configuration Variables

Config

Title

Default

Option

dCF01

(Future Use)

-

-

dCF02

Sensor Configuration

2

2, 5, 6, 9, 54, 64, 94

dCF03

Logging Interval (Minutes)

60

15, 30, 60, 120

dCF04

Thermistor Format

Short

Long

dCF05

Thermistor Sampling Type

A

A, b, C

dCF06

Controlled Atmosphere / Humidity Sampling Type

A

A, b

dCF07

Alarm Configuration USDA Sensor 1

A

Auto, On, Off

dCF08

Alarm Configuration USDA Sensor 2

A

Auto, On, Off

dCF09

Alarm Configuration USDA Sensor 3

A

Auto, On, Off

dCF10

Alarm Configuration Cargo Sensor

A

Auto, On, Off

Figure 4.11  Standard Configuration Download Report

Fig_standard_configuration_report.jpg 

Table 4–3  DataCORDER Standard Configurations

Standard Config

Description

2 sensors (dCF02=2)

2 thermistor inputs (supply & return)

5 sensors (dCF02=5)

2 thermistor inputs (supply & return)

3 USDA thermistor inputs

6 sensors (dCF02=6)

2 thermistor inputs (supply & return)

3 USDA thermistor inputs

1 humidity input

9 sensors (dCF02=9)

Not Applicable

6 sensors (dCF02=54)

2 thermistor inputs (supply & return)

3 USDA thermistor inputs

1 cargo probe (thermistor input)

7 sensors (dCF02=64)

2 thermistor inputs (supply & return)

3 USDA thermistor inputs

1 humidity input

1 cargo probe (thermistor input)

4.7.6Sampling Type (dCF05 & dCF06)

Three types of data sampling are available: average, snapshot and USDA. When configured to average, the aver­age of readings taken every minute over the recording period is recorded. When configured to snapshot, the sen­sor reading at the log interval time is recorded. When USDA is configured, the supply and return temperature readings are averaged and the three USDA probe readings are snapshot.

4.7.7Alarm Configuration (dCF07 - dCF10)

The USDA and cargo probe alarms may be configured to OFF, ON or AUTO.

If a probe alarm is configured to OFF, the alarm for this probe is always disabled.

If a probe alarm is configured to ON, the associated alarm is always enabled.

If the probes are configured to AUTO, they act as a group. This function is designed to assist users who keep their DataCORDER configured for USDA recording, but do not install the probes for every trip. If all the probes are dis­connected, no alarms are activated. As soon as one of the probes is installed, all of the alarms are enabled and the remaining probes that are not installed will give active alarm indications.

4.7.8DataCORDER Power Up

The DataCORDER may be powered up in any one of four ways:

1.Normal AC power: The DataCORDER is powered up when the unit is turned on via the stop-start switch.

2.Controller DC battery pack power: If a battery pack is installed, the DataCORDER will power up for commu­nication when an interrogation cable is plugged into an interrogation receptacle.

3.External DC battery pack power: A 12 volt battery pack may also be plugged into the back of the interrogation cable, which is then plugged into an interrogation port. No controller battery pack is required with this method.

4.Real Time Clock demand: If the DataCORDER is equipped with a charged battery pack and AC power is not present, the DataCORDER will power up when the real time clock indicates that a data recording should take place. When the DataCORDER is finished recording, it will power down.

During DataCORDER power-up, while using battery-pack power, the controller will perform a hardware voltage check on the battery. If the hardware check passes, the controller will energize and perform a software battery volt­age check before DataCORDER logging. If either test fails, the real time clock battery power-up will be disabled until the next AC power cycle. Further Data CORDER temperature logging will be prohibited until that time.

An alarm will be generated when the battery voltage transitions from good to bad indicating that the battery pack needs recharging. If the alarm condition persists for more than 24 hours on continuous AC power, the battery pack needs replacement.

4.7.9Pre-trip Data Recording

The DataCORDER will record the initiation of a pre-trip test (refer to Section 4.6) and the results of each of the tests included in pre-trip. The data is time-stamped and may be extracted via the Data Retrieval program. Refer to Table 4–9 for a description of the data stored in the DataCORDER for each corresponding Pre-trip test.

4.7.10DataCORDER Communications

Data retrieval from the DataCORDER can be accomplished by using one of the following: DataReader, DataLINE, or a communications interface module.

A DataReader, DataLINE or a communications interface module display of Communication Failed is caused by faulty data transfer between the DataCORDER and the data retrieval device. Common causes include:

1.Bad cable or connection between DataCORDER and data retrieval device.

2.PC communication port(s) unavailable or mis-assigned.

3.Chart Recorder Fuse (FCR) blown.

Configuration identification for the models covered herein may be obtained on the Container Products Group Infor­mation Center by authorized Carrier Transicold Service Centers.

a.DataReader

The Carrier Transicold Data Reader (see Figure 4.12) is a simple to operate handheld device designed to extract data from the DataCORDER and upload it to a PC. The Data Reader has the ability to store multiple data files. Refer to Data Retrieval manual 62-10629 for a more detailed explanation of the DataReader.

Figure 4.12  Data Reader

Fig_datareader.jpg 

b.DataBANKTM Card

The DataBANKTM card is a PCMCIA card that interfaces with the controller through the programming slot and can download the data at a much faster rate, when compared to the PC or DataReader. Files downloaded to Data­BANK card files are accessible through an Omni PC Card Drive. The files can then be viewed using the DataLINE software.

c.DataLINE

The DataLINE software for a personal computer is supplied on both floppy disks and CD. This software allows interrogation, configuration variable assignment, screen view of the data, hard copy report generation, cold treat­ment probe calibration, and file management. Refer to Data Retrieval manual 62-10629 for a more detailed expla­nation of the DataLINE interrogation soft ware. The DataLINE manual may be found on the Internet at www.container.carrier.com.

d.Communications Interface Module

The communications interface module is a slave module, which allows communication with a master central moni­toring station. The module will respond to communication and return information over the main power line.

With a communications interface module installed, all functions and selectable features that are accessible at the unit may be performed at the master station. Retrieval of all DataCORDER reports may also be performed. Refer to the master system technical manual for further information.

4.7.11USDA Cold Treatment

Sustained cold temperature has been employed as an effective post-harvest method for the control of Mediterra­nean and certain other tropical fruit flies. Exposing infested fruit to temperatures of 2.2°C (36°F) or below for spe­cific periods results in the mortality of the various stages of this group of insects.

In response to the demand to replace fumigation with this environmentally sound process, Carrier has integrated Cold Treatment capability into its microprocessor system. These units have the ability to maintain supply air tem­perature within one quarter degree Celsius of set point and record minute changes in product temperature within the DataCORDER memory, thus meeting USDA criteria. Information on USDA is provided in the following sub-paragraphs.

a.USDA Recording

A special type of recording is used for USDA cold treatment purposes. Cold treatment recording requires three remote temperature probes be placed at prescribed locations in the cargo. Provision is made to connect these probes to the DataCORDER via receptacles located at the rear left-hand side of the unit. Four or five receptacles are provided. The four 3-pin receptacles are for the probes. The 5-pin receptacle is the rear connection for the Interrogator. The probe receptacles are sized to accept plugs with tricam coupling locking de vices. A label on the back panel of the unit shows which receptacle is used for each probe.

The standard DataCORDER report displays the supply and return air temperatures. The cold treatment report dis­plays USDA #1, #2, #3, and the supply and return air temperatures. Cold treatment recording is backed up by a battery so recording can continue if AC power is lost.

4.7.12USDA/ Message Trip Comment

A special feature in DataLINE allows the user to enter a USDA (or other) message in the header of a data report. The maximum message length is 78 characters. Only one message will be recorded per day.

4.7.13USDA Cold Treatment Procedure

The following is a summary of the steps required to initiate a USDA Cold Treatment:

a.Calibrate the three USDA probes by ice bathing the probes and performing the calibration function with the DataReader or DataLINE. This calibration procedure determines the probe offsets and stores them in the controller for use in generating the cold treatment report. Refer to the Data Retrieval manual 62-10629 for more details.

b.Pre-cool the container to the treatment temperature or below.

c.Install the DataCORDER module battery pack (if not already installed).

d.Place the three probes. The probes are placed into the pulp of the product (at the locations defined in the following table) as the product is loaded.

Sensor 1

Place in pulp of the product located next to the return air intake.

Sensor 2

Place in pulp of the product five feet from the end of the load for 40 foot containers, or three feet from the end of the load for 20 foot containers. This probe should be placed in a center carton at one-half the height of the load.

Sensor 3

Place in pulp of product five feet from the end of the load for 40 foot containers or three feet from the end of the load for 20 foot containers. This probe should be placed in a carton at a side wall at one-half the height of the load.

e.To initiate USDA recording, connect the personal computer and perform the configuration as follows, using the DataLINE software:

1.Enter ISO header information.

2.Enter a trip comment if desired.

3.Configure the DataCORDER for five probes (s, r, P1, P2, P3) (dcf02=5).

4.Configure the logging interval for one hour.

5.Set the sensor configuration to “USDA”.

6.Configure for two byte memory storage format (dcf04=LONG).

7.Perform a “trip start”.

4.7.14DataCORDER Alarms

The alarm display is an independent DataCORDER function. If an operating parameter is outside of the expected range or a component does not return the correct values to the DataCORDER, an alarm is generated. The Data­CORDER contains a buffer of up to eight alarms. A listing of the DataCORDER alarms is provided in Table 4–10, page. Refer to Section 4.7.7 for configuration information.

To display alarm codes:

a.While in the Default Display mode, press the ALT. MODE & ALARM LIST keys. This accesses the Data­CORDER Alarm List Display Mode, which displays any alarms stored in the alarm queue.

b.To scroll to the end of the alarm list, press the UP ARROW. Depressing the DOWN ARROW key will scroll the list backward.

c.The left display will show “AL#” where # is the alarms number in the queue. The right display will show “AA##”, if the alarm is active, where ## is the alarm number. “IA##”, will show if the alarm is inactive

d.“END” is displayed to indicate the end of the alarm list if any alarms are active. “CLEAr” is displayed if all the alarms in the list are inactive.

e.If no alarms are active, the alarm queue may be cleared. The exception to this rule is the DataCORDER alarm queue Full alarm (AL91), which does not have to be inactive in order to clear the alarm list. To clear the alarm list:

1.Press the ALT. MODE & ALARM LIST keys.

2.Press the UP/DOWN ARROW key until “CLEAr” is displayed.

3.Press the ENTER key. The alarm list will clear and “-----” will be displayed.

4.Press the ALARM LIST key. “AL” will show on the left display and “-----” on the right display when there are no alarms in the list.

5.Upon clearing of the alarm queue, the alarm light will be turned off.

4.7.15ISO Trip Header

DataLINE provides the user with an interface to view/ modify current settings of the ISO trip header through the ISO Trip Header screen.

The ISO Trip Header screen is displayed when the user clicks on the “ISO Trip Header” button in the “Trip Func­tions” Group Box on the System Tools screen.

F9 function - Provides the user with a shortcut for manually triggering the refresh operation. Before sending modi­fied parameter values, the user must ensure that a successful connection is established with the controller.

If the connection is established with the DataCORDER, the current contents of the ISO Trip Header from the Data­CORDER will be displayed in each field. If the connection is not established with the DataCORDER, all fields on the screen will be displayed as “Xs”. If at any time during the display of the ISO Trip Header screen the connection is not established or is lost, the user is alerted to the status of the connection.

After modifying the values and ensuring a successful connection has been made with the DataCORDER, click on the “Send” button to send the modified parameter values.

The maximum allowed length of the ISO Trip Header is 128 characters. If the user tries to refresh the screen or close the utility without sending the changes made on the screen to the DataCORDER, the user is alerted with a message.

Table 4–4  Controller Configuration Variables

Config

Title

Default

Option

CnF02

Evaporator Fan Speed

dS (Dual)

SS (Single)

CnF03

Control Sensors

FOUr

duAL

CnF04

Dehumidification Mode

On

OFF

CnF08

Single Phase/3-Phase Evaporator Fan Motor

1Ph

3Ph

CnF09

Refrigerant Selection

r134a

r744

CnF11

Defrost “Off” Selection

noOFF

OFF

CnF15

Discharge Temperature Sensor

Out

In

CnF16

DataCORDER Present

On (Yes)

(Not Allowed)

CnF17

Discharge Pressure Sensor

Out (No)

In (Yes)

CnF18

Heater

Old (Low Watt)

nEW (High Watt)

CnF20

Suction Pressure Sensor

Out (No)

In (Yes)

CnF22

Economy Mode Option

OFF

Std, Full

CnF23

Defrost Interval Timer Save Option

noSAv

SAv

CnF24

Advanced Pre-trip Enhanced Test Series Option

Auto

Auto2, Auto 3

CnF25

Pre-trip Test Points/Results Recording Option

rSLtS

dAtA

CnF26

Heat Lockout Change Option

Set to -10C

Set to -5C

CnF27

Suction Temperature Display Option

Out

In

CnF28

Bulb Mode Option

NOr

bULb

CnF31

Probe Check Option

SPEC

Std

CnF32

Single Evaporator Fan Option

2EF0

(Not Allowed)

CnF33

Snap Freeze Option

OFF

SnAP

CnF34

Degree Celsius Lockout Option

bOth

F

CnF37

Electronic Temperature Recorder

rEtUR

SUPPL, bOth

CnF41

Lower DTT Setting

Out

In

CnF44

eAutoFresh Enabled

Out

LO, UP

CnF45

Low Humidity Enabled

Out

In

CnF47

Fresh Air Vent Position Sensor

OFF

UP, LOW, CUStOM

CnF49

DataCORDER Configuration Restore

OFF

On

CnF50

Enhanced Bulb Mode Selection

OFF

Bulb, dEHUM

CnF51

Timed Defrost Disable

0

0-out, 1-in

CnF52

Oil Return Algorithm

1

0-out, 1-in

CnF53

Water Cool Oil Return Logic

0

0-out, 1-in

CnF55

TXV Boost Relay

0

0-out, 1-in

CnF56

TXV Boost Circuit

0

0-out, 1-in

CnF59

Electronic Expansion Valve

0

1-EC, 2-KE, 3- NA

CnF60

Compressor-Cycle Perishable Cooling

0

0-out, 1-in

CnF61

ACT ASC Control Enable

0

0-out, 1-in

CnF62

Extended Temperature Control Enable

0

0-on, 1-in

CnF63

CCPC Pre-trip/Tripstart Default State

0

0-on, 1-off

CnF64

Evaporator Fan Pulsing Logic Enable

0

0-in, 1-out

Configuration numbers not listed are not used in this application. These items may appear when load­ing configuration software to the controller but changes will not be recognized by the controller pro­gramming.

Table 4–5  Controller Function Codes

Code

Title

Description

If the function is not applicable, the display will read “-----”

Display Only Functions

Cd01

Capacity Modulation (%)

Displays the DUV percent closed. The right display reads 100% when the valve is fully closed. The valve will usually be at 10% on start up of the unit except in very high ambient temperatures.

Cd03

Compressor Motor Current

The current sensor measures current draw in lines L1 & L2 by all of the high voltage components. It also measures current draw in compressor motor leg T3. The compressor leg T3 current is displayed.

Cd04

Cd05

Cd06

Line Current Phase A

Line Current Phase B

Line Current Phase C

The current sensor measures current on two legs. The third unmeasured leg is calculated based on a current algorithm. The current measured is used for control and diagnostic purposes. For control processing, the highest of the Phase A and B current values is used for current limiting purposes. For diagnostic processing, the current draws are used to monitor component energization. Whenever a heater or a motor is turned ON or OFF, the current draw increase/reduction for that activity is measured. The current draw is then tested to determine if it falls within the expected range of values for the component. Failure of this test will result in a pre-trip failure or a control alarm indication.

Cd07

Main Power Voltage

The main supply voltage is displayed.

Cd08

Main Power

Frequency

The value of the main power frequency is displayed in Hertz. The frequency displayed will be halved if either fuse F1 or F2 is bad (alarm code AL21).

Cd09

Ambient

Temperature

The ambient sensor reading is displayed.

Cd10

Evaporator

Temperature Sensor

Evaporator temperature sensor reading is shown on the right display.

Cd11

Compressor Dome Temperature / Discharge Temperature

Compressor discharge temperature sensor reading, using compressor dome temperature, is displayed.

Cd12

Compressor Suction Port Pressure / Evaporator Pressure

Reading for evaporator pressure transducer (EPT) is shown on the left display; Press ENTER at Cd12 to show reading for compressor suction port pressure on right display.

Cd14

Compressor

Discharge Pressure

Compressor discharges pressure transducer reading is displayed.

Cd15

Digital Unloader Valve

The status of the valve is displayed (Open - Closed).

Cd16

Compressor Motor Hour Meter / Unit Run Time Hour Meter

This code displays the compressor motor hours. User can view unit run time by pressing the ENTER key while in Cd16. Total hours are recorded in increments of 10 hours (i.e., 3000 hours is displayed as 300).

The Compressor Motor Hour Meter display can be reset to 0 by pressing and holding the ENTER key for 5 seconds. The Unit Run Time Hour Meter cannot be reset.

Cd17

Relative Humidity %

Humidity sensor reading is displayed. This code displays the relative humidity, as a percent value.

Cd18

Software Revision Number

The software revision number is displayed.

Cd19

Battery Check

This code checks the Controller / DataCORDER battery pack. While the test is running, “btest” will flash on the right display, followed by the result. “PASS” will be displayed for battery voltages greater than 7.0 volts. “FAIL” will be displayed for battery voltages between 4.5 and 7.0 volts, and “-----” will be displayed for battery volt ages less than 4.5 volts. After the result is displayed for four seconds, “btest” will again be displayed, and the user may continue to scroll through the various codes.

Cd20

Config / Model Number

This code indicates the dash number of the model for which the Controller is configured (i.e., if the unit is a 69NT40-551-100, the display will show “51100”). To display controller configuration database information, press ENTER. Values in “CFYYMMDD” format are displayed if the controller was configured with a configuration card or with a valid OEM serial port configuration update; YYMMDD represents the publication date of the model configuration database.

Cd21

Capacity Mode

The mode of operation is displayed (Unloaded - Standard - Economized).

Cd22

Compressor State

The status of the compressor is displayed (Off, On).

Cd23

Evaporator Fan State

Displays the current evaporator fan state (high, low or off).

Cd25

Compressor Run Time Remaining

Until Defrost

This code displays the time remaining until the unit goes into defrost (in tenths of an hour). This value is based on the actual accumulated compressor running time.

Cd26

Defrost Temperature Sensor Reading

Defrost temperature sensor reading is displayed.

Configurable Functions

NOTE:

Function codes Cd27 through Cd37 are user-selectable functions. The operator can change the value of these functions to meet the operational needs of the container.

Cd27

Defrost Interval (Hours or Automatic)

There are three modes for defrost initiation: user-selected timed intervals, automatic control, and PuLs. The user-selected values are (OFF), 3, 6, 9, 12, 24 hours, AUTO, or PuLs. The factory default is AUTO. Automatic defrost starts with an initial defrost at three hours, then the interval to the next defrost is adjusted based on the accumulation of ice on the evaporator coil. Following a start-up or after termination of a defrost, the time will not begin counting down until the defrost temperature sensor (DTS) reading falls below set point. If the reading of DTS rises above set point any time during the timer count down, the interval is reset and the countdown begins over. If DTS fails, alarm code AL60 is activated and control switches over to the return temperature sensor. The controller will act in the same manner as with the DTS except the return temperature sensor reading will be used. For information on PuLs, refer to Defrost Pulsing Section 4.3.19.

Defrost Interval Timer Value (Configuration variable CnF23): If the software is configured to “SAv” (save) for this option, the value of the defrost interval timer will be saved at power down and restored at power up. This option prevents short power interruptions from resetting an almost expired defrost interval, and possibly delaying a needed defrost cycle.

NOTE:

The defrost interval timer counts only during compressor run time.

Cd28

Temperature

Units (Degrees C or Degrees F)

This code determines the temperature units (C or F) that will be used for all temperature displays. The user selects C or F by selecting function code Cd28 and pushing the ENTER key. The factory default value is Celsius units.

NOTE:

This function code will display “-----” if CnF34 is set to F.

Cd29

Failure Action (Mode)

If all of the control sensors are out of range (alarm code AL26) or there is a probe circuit calibration failure (alarm code AL27), the unit will enter the shutdown state defined by this setting. The user selects one of four possible actions as follows:

A - Full Cooling (Compressor is on, economized operation.)

B - Partial Cooling (Compressor is on, standard operation.)

C - Evaporator Fan Only (Evaporator fans on high speed, not applicable with frozen set points.)

D - Full System Shutdown - Factory Default (Shut down every component in unit.)

Cd30

In-Range Tolerance

The in-range tolerance will determine the band of temperatures around the set point which will be designated as in-range. If the control temperature is in-range, the in-range light will be illuminated. There are four possible values:

1 = +/- 0.5°C (+/- 0.9°F)

2 = +/- 1.0°C (+/- 1.8°F)

3 = +/- 1.5°C (+/- 2.7°F)

4 = +/- 2.0°C (+/- 3.6°F) - Factory Default

Cd31

Stagger Start Offset Time (Seconds)

The stagger start offset time is the amount of time that the unit will delay at start-up, thus allowing multiple units to stagger their control initiation when all units are powered up together. The eight possible offset values are:

0 (Factory Default), 3, 6, 9, 12, 15, 18, or 21 seconds

Cd32

System Current Limit

(Amperes)

The current limit is the maximum current draw allowed on any phase at any time. Limiting the unit's current reduces the load on the main power supply. When desirable, the limit can be lowered. Note, however, that capacity is also reduced. The five values for 460 VAC operation are: 15, 17, 19, 21, or 23 amperes. The factory default setting is 21 amperes.

Cd33

Humidity Setpoint

Relative humidity set point is available only on units configured for dehumidification. When the mode is activated, the control probe LED flashes on and off every second to alert the user. If not configured, the mode is permanently deactivated and “-----” will display. The value can be set to “OFF,” “TEST,” or a range of 65 to 95% relative humidity in increments of 1%. [If bulb mode is active (code Cd35) and “Lo” speed evaporator motors are selected (code Cd36), then set point ranges from 60 to 95%.] When “TEST” is selected or test set point is entered, the heat LED should illuminate, indicating that dehumidification mode is activated. After a period of five minutes in the “TEST” mode has elapsed, the previously selected mode is reinstated.

Cd34

Economy Mode (On-Off)

Economy mode is a user selectable mode of operation provided for power saving purposes.

Cd35

Bulb Mode

Bulb mode is a user selectable mode of operation that is an extension of dehumidification control (Cd33). If dehumidification is set to “Off,” code Cd35 will display “Nor” and the user will be unable to change it. After a dehumidification set point has been selected and entered for code Cd33, the user may change code Cd35 to “bulb.” After bulb has been selected and entered, the user may utilize function codes Cd36 and Cd37 to make the desired changes.

Cd36

Evaporator Fan Speed

This code is enabled only if in the dehumidification mode (code Cd33) and bulb mode (Cd35) has been set to “bulb.” If these conditions are not met, “alt” will be displayed (indicating that the evaporator fans will alternate their speed) and the display cannot be changed. If a dehumidification set point has been selected along with bulb mode, “alt” may be selected for alternating speed, “Lo” for low speed evaporator fan only, or “Hi” for high speed evaporator fan only. If a setting other than “alt” has been selected and bulb mode is deactivated in any manner, the selection reverts back to “alt.”

Cd37

Variable DTT Setting

(Bulb Mode)

This code, as with function code Cd36, is used in conjunction with bulb mode and dehumidification. If bulb mode is active, this code allows the user to change the temperature above which defrost will terminate. It allows the user to change the setting within a range of 4°C to 25.6°C in 0.1°C (0.2°F) increments. This value is changed using the UP/DOWN ARROW keys, followed by the ENTER key when the desired value is displayed. If bulb mode is deactivated, the DTS setting re turns to the default.

Cd38

Secondary Supply Temperature Sensor

Code Cd38 will display the current supply recorder sensor (SRS) reading for units configured for four probes. If the unit is configured with a DataCORDER, Cd38 will display “-----.” If the DataCORDER suffers a failure, (AL55) Cd38 will display the supply recorder sensor reading.

Cd39

Secondary Return Temperature Sensor

Code Cd39 will display the current return recorder sensor (RRS) reading for units configured for four probes. If the unit is configured with a DataCORDER, Cd39 will display “-----.” If the DataCORDER suffers a failure, (AL55) Cd39 will display the return recorder sensor reading.

Cd40

Container Identification Number

Code Cd40 is configured at commissioning to read a valid container identification number. The reading will not display alpha characters; only the numeric portion of the number will display.

Cd41

Valve Override

SERVICE FUNCTION: This code is used for troubleshooting, and allows manual positioning of the economizer solenoid valve, electronic expansion valve, and digital unloader valve. Provides readings such as: Percent Capacity, EEV, Capacity Mode, LIV, and DUV. Refer to Section 7.16 for operating instructions.

Cd43

eAutoFresh Mode

Code Cd43 is used to select the mode of operation for the eAutoFresh slides. Associated parameters can also be selected from submenus: OFF, USER, DELAY, TEST and gASLM. If the unit is not configured for eAutoFresh, Cd43 will

display “-----.”

Cd44

eAutoFresh Values / CO2 Sensor Status

Code Cd44 displays the eAutoFresh CO2 and O2 values (CO2 and O2) and CO2 and O2 limits (CO2LIM and O2LIM), respectively. If the unit is not configured for eAutoFresh, Cd44 will display “-----.”

Cd45

Vent Position Sensor (VPS) Position

Unless AL50 is active or CnF47 is OFF, the fresh air flow (CMH/CFM) is displayed. This function code will automatically activate for 30 seconds and display when a vent position change occurs.

Cd46

Airflow Display Units

This code displays the airflow units to be displayed for Cd 45. Options are CF, CM, or bOth (dependent on the setting of Cd28 or pressing of the C/F key).

Cd47

Variable Economy Temperature Setting

Code Cd47 is used with optional economy mode. Values are 0.5°C-4.0°C, default is 3.0°C. If unit is not configured for economy mode, “----” will be displayed.

Cd48

Dehumidification / Bulb Cargo Mode Parameter Selection

Code Cd48 is used both when dehumidification set point is set above 65% RH and below 64% RH. When dehumidification set point is set above 65% RH, select goes to LO if it had been set to hi. When dehumidification set point is set below 64% RH, select goes to Alt if it had been set to LO.

Cd49

Days Since Last Successful Pre-trip

Code Cd49 will display the time period (days) since the last successful pre-trip completion. Press ENTER repeatedly to display last pre-trip completion in Auto, Auto 1, and Auto 2 modes.

Cd50

Quest Enable / Disable

Code 50 allows selection of CCPC mode. The user can press ENTER, then arrow keys, then ENTER again to enable (On) or suspend (OFF) CCPC mode. If CCPC operation is On, it may be suspended due to one of the following conditions:

“SEtPt” =Set point is too low.

“CAHUM”= CA or humidity control is active

“ACT”=ACT is active.

“FAIL”=Return temperature probe has failed.

“PrtrP”=Pre-trip is active.

“C LIM”= Cool limit logic is active.

“PULL”=Unit is in pulldown mode.

Cd51

Automatic Cold Treatment (ACT) Mode Parameter Selection

Code Cd51 initially displays countdown timer increments of 1 day, 1 hour with the temperature default. Pressing ENTER allows selection of within the current menu and proceeds to the next menu. After five seconds of no activity, the display reverts to normal system display, but retains the parameters previously selected.

“ACt” = “On,” “Off” or “----”. The default is Off.

“trEAt”=C /F in 0.1 degree increments. The default is 0.0°C.

“DAyS”= “0-99” increments of 1. The default is 0.

“ProbE”=probe positions (example 12°4). The default is ----.

“SPnEW”= C /F in 0.1 degree increments. The default is 10.0°C.

Cd53

Automatic Setpoint Change (ASC) Mode Parameter Selection

Code Cd53 initially displays countdown timer increments of 1 day, 1 hour with the temperature default. Pressing ENTER allows selection of within the current menu and proceeds to the next menu. After five seconds of no activity, the display reverts to normal system display, but retains the parameters previously selected.

“ASC”=”On” or “Off” The default is Off.

“NSC”=”1-2”

“SP 0"=C /F in 0.1 degree increments. The default is 10.0°C.

“DAY 0"= “0-99” increments of 1. The default is 1.

“SP 1"=C /F in 0.1 degree increments. The default is 10.0°C.

“DAY 1"= “0-99” increments of 1. The default is 1.

“SP 2"=C /F in 0.1 degree increments. The default is 10.0°C.

Cd54

Suction Port Superheat / Electronic Expansion Valve Status

Reading for evaporator superheat is shown on the right display. Press ENTER at Cd54 to show reading for EEV position (in%) on left display.

Cd55

Discharge

Superheat

Code Cd55 will display the discharge superheat values in C /F as calculated by the discharge temperature minus the discharge saturation temperature as calculated from discharge pressure. “-----” will be displayed if selection is not valid.

Cd58

Water Pressure Switch / Condenser Fan Switch State or Override Logic State

Code Cd58 will display “CLOSE” if the WPS or CFS switch contacts are closed or that these options are not installed. “OPEn” is displayed when the WPS or CFS switch contacts are open. When the WPS/CFS Override Logic is “TRUE”, the right display will flash on all units.

Cd59

Pump Down Logic

Code Cd59 allows operation of the pump down logic control. The display will flash between “STArT PdN” and “PrESS EnTEr”. Once the operator confirms continuation of the sequence, pump down logic begins. If pump down logic is completed within 20 minutes, the unit will turn off and the display will flash “P dN DOnE” and “SHUT OFF”. The operator must shut off the unit. If the pump down logic is not completed within 20 minutes, the unit will return to its previous control condition.

Cd60

Evaporator Fan

Pulsing Temperature Setting

CD60 contains a selectable temperature range used to determine the engagement point of the Evaporator Fan Pulsing logic. Default setting is -18.1°C. The user may change the temperature by pressing enter, then scrolling to the desired temperature using either arrow key. Press Enter to accept the change. The temperature setting will be retained until either a Pretrip or Trip Start is initiated at which time the temperature will set to the default setting.

Cd62

High Speed Evaporator Fan Setting

Cd62 is used to force evaporator fan speed to high while temperature control is being performed in the perishable setpoint range. When set to “On”, evaporator fans operate in high speed regardless of any other active option that can control evaporator fan speed.

Following a power cycle, the state of the function select code is retained at its state prior to the power cycle. If “On”, this function select code will be set to “OFF” when any trip start occurs or any pre-trip test is initiated.

“-----” will be displayed if setpoint is in frozen range or if CnF66 is configured OFF.

Cd63

FuelWise

Cd63 is used to enable FuelWise.

Following a power cycle, the state of the function select code is retained at its state prior to the power cycle if CNF72 = Default ON else if Default OFF this will be set to OFF. If “On”, this function select code will be set to “OFF” when any trip start occurs or any pretrip test is initiated.

Event 120 shall be logged when ever CD63 is Turned ON OR if CD63 state is ON at Midnight.

“-----” will be displayed if Cnf72 is configured OFF.

Cd65

TripWise

If the function is off, display "OFF". If the function is on, display "ON".

“-----” will be displayed if the TripWise option is not active for the current configuration.

Press the ENTER key. The existing entry will flash. Use the Arrow keys to alternate between OFF and ON. Press ENTER again to set the Expiration Interval.

Left display: “dAyS”

Right display: Expiration Interval 2 through 365 in one day increments.

Default value is 30.

Cd66

Instantaneous Power (kW)

Real power in kW currently being used by the system.

Value is “-----“,“ nnn.n

Display “-----“ if not configured else nnn.n

Cd67

Total Power (kW-hr)

Energy used by the system, in kW-hrs, since last Trip Start.

Value is “-----“,“ nnnnn

Display “-----“ if not configured else nnnnn

Cd70

Temp Setpoint Lock

Cd70 locks out setpoint selection, requiring the user to manually turn the lock off, prior to making a setpoint change. If the setpoint lock is “ON”, and the user attempts to enter a new setpoint, a message “SPLK” (Setpoint Lock) is in the left display and “ON” in the right display for five seconds.

Press the ENTER key. “SPLK” will display along with the current setting of “ON” or “OFF”. Use the Arrow keys to change the selection - the new selection will then flash for five seconds. Press the ENTER key to confirm the new selection.

An event will be recorded in the DataCorder each time the action of turning it “ON” or “OFF” is taken.

Default setting is “OFF”. Unit will default to “OFF” with the selection of PTI or a TripWise on the unit.

Figure 4.13  Alarm Troubleshooting Sequence

Fig_alarm_troubleshooting_sequence.jpg 

Table 4–6  Controller Alarm Indications

Code

Cause

Components

Troubleshooting

Corrective Actions

AL03

Loss of

Superheat Control

Superheat has remained below 1.66°C (3°F) degrees for five minutes continuously while compressor running. Compressor drawing more than 2.0 amps, compressor pressure ratio is greater than 1.8, and Electronic Expansion Valve (EEV) is at 0% open.

Electronic Expansion Valve (EEV)

Check the operation of the EEV using Cd41.

Replace EEV if

defective.

Evaporator Temperature Sensor(s) ETS & ETS1.

Verify accuracy of temperature sensors, refer to Sensor Checkout Procedure Section 7.19.1.

Replace ETS or ETS1

if defective.

Evaporator Fans

Confirm fans

operating properly.

Replace fan(s) if defective, refer to

EVAPORATOR FAN MOTOR ASSEMBLY Section 7.10.

AL05

Manual

Defrost Switch

Failure

Controller has detected continuous Manual Defrost Switch activity for five minutes or more.

Keypad

Power cycle the unit.

Resetting the unit may correct problem, monitor the unit.

If the alarm reappears after 5 minutes replace the keypad.

AL06

Keypad or Keypad

Harness Fail

Controller has detected one of the keypad keys is continuously activity.

Keypad or

Harness

Power cycle the unit.

Resetting the unit may correct problem, monitor the unit.

If the alarm reappears replace the keypad and harness.

AL07

Fresh Air Vent Open with

Frozen Set Point

The VPS is reading greater than 0 CMH while unit is in frozen mode.

Vent Position Sensor (VPS)

Manually reposition vent and confirm using Cd45. Refer to VENT POSITION SENSOR SERVICE Section.

If unable to obtain zero reading, replace defective VPS.

AL08

High

Compressor Pressure Ra­tio

Controller detects discharge pressure to suction pressure ratio is too high.

The controller will attempt to correct the situation by restarting the compressor.

Discharge

Pressure

Transducer (DPT)

Confirm accurate DPT pressure readings, refer to MANIFOLD GAUGE SET Section 7.2.

Replace DPT if defective.

AL10

CO2 Sensor Failure

Alarm 10 is triggered when the CO2 sensor voltage is operating outside of the 0.9 v to 4.7 v range, or if the sensor is out of range.

This is a display alarm and has no associated failure action.

Refer to eAutoFresh manual.

The alarm is triggered off when voltage is within operating range.

AL14

Phase

Sequence

Detect Fault

Controller is unable to determine the correct phase relationship.

N/A

Power cycle the unit.

Resetting the unit may correct problem, monitor the unit.

Wiring

Check unit wiring.

Confirm pressure readings during start-up; suction pressure should decrease and discharge pressure should increase.

Correct wiring.

Current Sensor

Check Cd41, right most digit:

If display is 3 or 4 check compressor / sensor wiring.

If display is 5 the current sensor is defective.

Replace current

sensor if defective.

AL16

Compressor Current High

Compressor current draw is over the calculated maximum for 10 minutes.

Current Sensor

Compare Cd3 to actual measured current at wire T1-T2 or T3 going to the compressor contactor. If there is a difference, determine whether this is caused by current sensor or amp clamp tool.

Replace current

sensor if defective.

Amperage is

indeed too high.

Confirm supply voltage/frequency is within specification and balanced according to Electrical Data Section 3.3.

Correct power supply.

Operating

Conditions

Make sure system pressures are relevant to

operating conditions.

Check air flow of

condenser.

Check Refrigerant charge, refer to

REFRIGERATION

SYSTEM SERVICE

Section 7.3.

Monitor Unit

Alarm is display only the alarm may clear itself during operation

If alarm remains active or is repetitive replace compressor at next available opportunity,

refer to COMPRESSOR Service Section 7.4.

AL17

Compressor Pressure Delta Fault

Compressor has attempted to start in both directions and fails to generate sufficient pressure differential between SPT and DPT.

N/A

Controller will attempt restart every 20 minutes and deactivate the alarm if successful.

Resume normal

operation.

Discharge Pressure Transducer (DPT)

Confirm accurate DPT pressure readings, refer to MANIFOLD GAUGE SET Section 7.2

Replace DPT if

defective.

Suction Pressure Transducer (SPT)

Confirm accurate SPT pressure readings, refer to MANIFOLD GAUGE SET Section 7.2.

Replace SPT if

defective.

Monitor unit

Alarm is display only the alarm may clear itself during operation.

If alarm remains active or is repetitive replace compressor at next available opportunity.

AL18

Discharge Pressure High

Discharge pressure is over the maximum for 10 minutes within the last hour.

Restrictions in the refrigeration

system.

Ensure Liquid Line Service Valve is fully open.

Open Liquid Line Service Valve as needed.

Filter Drier

Check the filter drier, if it is iced up or very cold it indicates that the filter drier needs replacement.

Replace the filter drier if needed, refer to FILTER DRIER Service Section 7.8.

Condenser Fan

Check Condenser Fan for proper operation.

Correct as required.

Discharge

Pressure

Transducer (DPT)

Confirm accurate DPT pressure readings, refer to MANIFOLD GAUGE SET Section 7.2.

Replace DPT

if defective.

Non-condensables in the

refrigeration

system.

With the unit off allow system to stabilize to ambient temperature. Check system pressure against PT Chart for 134a, refer to Table 7–5.

Correct as required, refer to Refrigerant Charge Section 7.3.5.

Refrigerant

Check refrigerant level.

Correct as required, refer to Refrigerant Charge Section 7.3.5.

AL19

Discharge Tempera­ture High

Discharge temperature exceeds 135°C (275°F) for 10 minutes within the last hour.

Restrictions in the refrigeration

system.

Ensure the Discharge Service Valve is fully open.

Open the Discharge Service Valve as needed.

Check the unit for air flow restrictions.

Clean or remove any

debris from coils.

Non-condensables in the refrigeration system.

With the unit off allow system to stabilize to ambient temperature. Check system pressure against PT Chart for 134a, refer to Table 7–5.

Correct as required, refer to Refrigerant Charge Section 7.3.5.

Additional Alarms such as AL16, AL24.

Check compressor

operation.

If the alarm persists, it may indicate a failing compressor, replace the compressor, refer to COMPRESSOR

Service Section 7.4.

AL20

Control Con­tactor Fuse (F3)

Control power fuse (F3A or F3B) is open.

Check F3A, if the fuse is open:

Check PA, PB, CH coils for short to ground, if short is found:

Replace the

defective coil.

Replace the fuse.

Check F3B, if the fuse is open:

Check ESV coil resistance at TP7 to TP9, if short to ground, or if resistance is less than 4 ohms, coil is defective.

Check CF, ES, EF, HR coils for short to ground, if short is found, coil is defective.

Replace the

defective coil.

Replace the fuse.

Check Voltage at QC1:

If voltage is present, it indicates a defective microprocessor.

Refer to Controller

Service Section 7.17.

AL21

Control Cir­cuit Fuse (F1/F2)

One of the 18 VAC controller fuses (F1/F2) is open. Refer to Cd08.

System Sensors

Check system sensors for short to ground.

Replace defective

sensor(s)

Wiring

Check wiring for short to ground.

Repair as needed.

Controller

Controller may have an internal short.

Replace controller, refer to Controller Service Section 7.17.

AL22

Evaporator IP

Evaporator motor internal protector (IP) is open.

Evaporator Motor

Shut down unit, disconnect power, & check Evaporator Motor IP at plug connection

pins 4 & 6.

Replace defective

evaporator fan motor

refer to EVAPORATOR FAN MOTOR

Service Section 7.10.

AL23

Loss of

Phase B

Controller fails to

detect current draw.

Incoming Power

Check incoming

power source.

Correct power source as required.

AL24

Compressor IP

Compressor internal protector (IP) is open.

Compressor

Shut down unit disconnect power, & check resistance of compressor windings at contactor T1-T2, T2-T3.

Monitor unit, if alarm remains active or is repetitive replace the compressor at the next available opportunity,

refer to COMPRESSOR Service Section 7.4.

AL25

Condenser IP

Condenser fan motor internal protector (IP) is open.

Insufficient Air Flow

Shut down unit and check condenser fan for obstructions.

Remove obstructions.

Condenser Fan Motor

Shut down unit, disconnect power, & check Condenser Fan Motor IP at plug connection

pins 1 & 2.

Replace defective condenser fan motor, refer to Condenser Fan Motor Assembly Service Section 7.7.

AL26

All Sensors Failure: Sup­ply/Return Probes

Sensors out of range.

All sensors. detected as out of range

Perform Pre-trip P5:

If P5 passes, no further action is required.

If P5 fails, replace the defective sensor as determined by P5, refer to TEMPERATURE SENSOR Service Section 7.19.

AL27

Analog to

Digital Accu­racy Failure

Controller AD

converter faulty.

Controller

Power cycle the unit. If the alarm persists, it indicates a defective microprocessor.

Replace defective microprocessor, refer to Controller Service Section 7.17.

AL28

Low Suction Pressure

Suction pressure too low for normal

operation.

N/A

Power cycle the unit.

Resetting the unit may correct problem, monitor the unit.

Suction Pressure Transducer (SPT)

Confirm accurate SPT pressure readings, refer to MANIFOLD GAUGE SET Section 7.2.

Replace SPT if

defective.

Discharge Pressure Transducer (DPT)

Confirm accurate DPT pressure readings, refer to MANIFOLD GAUGE SET Section 7.2.

Replace DPT

if defective.

AL50

Air Vent Po­sition Sensor (VPS)

VPS Sensor

out of range.

Vent Position Sensor (VPS)

Make sure VPS

is secure.

Manually tighten panel.

If the alarm persists, replace the sensor or the assembly.

Replace VPS.

AL51

EEPROM

Failure

Controller Memory Failure

Controller

Pressing the ENTER key when “CLEAr” is displayed will result in an attempt to clear the alarm.

If action is successful (all alarms are inactive), alarm 51 will be reset.

Power cycle the unit. If the alarm persists, it indicates defective controller memory.

Replace defective controller, refer to Controller Service Section 7.17.

AL52

EEPROM Alarm List Full

Alarm list queue is full.

Active Alarms

Repair any alarms in the queue that are active. Indicated by “AA”.

Clear alarms, refer to CONTROLLER ALARMS Section 4.5.

AL53

Battery Pack Failure

Battery voltage low

Battery

If this alarm occurs on start up, allow a unit fitted with rechargeable batteries to operate for up to 24 hours to charge rechargeable batteries sufficiently. Once fully charged, the alarm will deactivate.

To clear the alarm press ENTER and ALT simultaneously at the startup of Cd19 (Battery Check).

If alarm persists, replace the battery pack, refer to Section 7.17.4 Battery Replacement.

AL54

Primary

Supply

Sensor (STS)

Invalid Supply Temperature Sensor (STS) reading.

Supply Temperature Sensor (STS)

Perform Pre-trip P5:

If P5 passes, no further action is required.

If P5 fails, replace the defective sensor as determined by P5, refer to TEMPERATURE SENSOR Service Section 7.19.

AL56

Primary

Return Sen­sor (RTS)

Invalid Return Temperature Sensor (RTS) reading.

Return Temperature Sensor (RTS)

Perform Pre-trip P5:

If P5 passes, no further action is required.

If P5 fails, replace the defective sensor as determined by P5, refer to TEMPERATURE SENSOR Service Section 7.19

AL57

Ambient

Sensor (AMBS)

Invalid Ambient Temperature Sensor (AMBS) reading.

Ambient Temperature Sensor (AMBS)

Test the AMBS, refer to Sensor Checkout Procedure Section 7.19.1.

Replace AMBS if defective, refer to TEMPERATURE SENSOR Service Section 7.19.

AL58

Compressor High Pres­sure Safety (HPS)

High pressure safety switch remains open for at least one minute.

High Pressure Switch (HPS)

Test the HPS; refer to Checking High Pressure Switch, Section 7.5.1.

Replace HPS if defective, refer to Sensor Replacement, Section 7.5.2

Refrigeration

System

Check unit for air flow

restrictions.

Clean or remove any

debris from coils.

AL59

Heater Ter­mination Thermostat (HTT)

Heat Termination Thermostat (HTT) is open.

Heat Termination Thermostat (HTT)

Check for 24 volts at test point TP10, if no voltage at TP10 after unit has reached set point HTT is open.

Replace HTT if defective, refer to Sensor Replacement Section 7.19.2.

AL60

Defrost Tem­perature Sensor (DTS)

Failure of the Defrost Temperature Sensor (DTS) to open.

Defrost Temperature Sensor (DTS)

Test the DTS; refer to Sensor Checkout Procedure Section 7.19.1

Replace the DTS if defective, refer to Sensor Replacement Section 7.19.2.

AL61

Heater Cur­rent Draw Fault

Improper current draw during heat or defrost mode.

Heater(s)

While in heat or defrost mode, check for proper current draw at heater contactors, refer to ELECTRICAL DATA Section 3.3.

Replace heater(s) if defective, refer to Section 7.9.2 Evaporator Heater Removal and Replacement.

Contactor

Check voltage at heater contactor on the heater side.

If no voltage present:

Replace heater contact or if defective.

AL63

Current Limit

Unit operating above current limit.

Refrigeration

System

Check unit for air flow

restrictions.

Clean or remove any debris from coils.

Check unit for proper

operation.

Repair as needed.

Power supply

Confirm supply voltage/frequency is within specification and balanced according to ELECTRICAL DATA Section 3.3.

Correct power supply.

Current limit set too low.

Check current limit setting Code Cd32.

The current limit can be raised (maximum of 23 amps) using Cd32.

AL64

Discharge Tempera­ture Sensor (CPDS)

Discharge Temperature sensor out of range.

Discharge temperature sensor (CPDS).

Test the CPDS; refer to Sensor Checkout Procedure, Section 7.19.1

Replace the CPDS if defective, refer to Sensor Replacement Section 7.19.2

AL65

Discharge Pressure Transducer (DPT)

Compressor Discharge Transducer is out of range.

Compressor Discharge Transducer (DPT)

Confirm accurate DPT pressure readings, refer to MANIFOLD GAUGE SET Section 7.2.

Replace DPT

if defective.

AL66

(SPT) Suc­tion Pressure Transducer, (EPT) Evap­orator Pres­sure Transducer

Suction Pressure Transducer (SPT) out of range.

Suction Pressure Transducer (SPT)

Confirm accurate EPT and SPT pressure readings, refer to MANIFOLD GAUGE SET Section 7.2.

- Performing a Pre-trip 5-9 test will also check the transducers.

Replace EPT/SPT

if defective.

Monitor

If the alarm persists, it may indicate a failing compressor, refer to COMPRESSOR Service Section 7.4.

AL67

Humidity

Sensor

Humidity Sensor (HS) reading out of range.

Humidity Sensor (HS)

Make sure the humidity sensor is properly connected in the socket.

Make sure the humidity sensor wires have not been damaged.

Monitor, replace HS if alarm persists.

AL69

Evaporator Temp Sen­sor (ETS1)

Evaporator Temperature Sensor (ETS1) out of range.

Evaporator Temperature Sensor (ETS1)

Test the ETS1, refer to Sensor Checkout Procedure Section 7.19.1.

Replace Evaporator Temperature Sensor (ETS1) if defective.

AL70

Secondary Supply

Sensor (SRS)

Secondary Supply Sensor (SRS) is

out of range.

Secondary Supply Sensor (SRS)

Perform Pre-trip P5:

If P5 passes, no further action is required.

If P5 fails, replace the defective sensor as determined by P5, refer to TEMPERATURE SENSOR Service Section 7.19.

AL71

Secondary

Return Sen­sor (RRS)

Secondary Return Sensor (RRS) is

out of range.

Secondary Return Sensor (RRS)

Perform Pre-trip P5:

If P5 passes, no further action is required.

If P5 fails, replace the defective sensor as determined by P5, refer to TEMPERATURE SENSOR Service Section 7.19.

AL72

Control Temp Out of Range

After the unit goes in-range for 30 minutes then out of range for a continuous 120 minutes.

Refrigeration

System

Ensure unit is operating correctly.

Power cycle unit.

Control Temperature is in In-range.

Any Pre-Trip mode, resets the timers.

Container doors

Check container doors, ensure they are properly closed and sealed

Close the container doors.

If the controller is configured for four probes without a DataCORDER, the DataCORDER alarms AL70 and AL71 will be processed as Controller alarms AL70 and AL71. Refer to Table 4–10.

ERR #

Internal

Microprocessor

Failure

The controller performs self-check routines. If an internal failure occurs, an “ERR”alarm will appear on the display. This is an indication the controller needs to be re placed.

ERROR

DESCRIPTION

ERR 0-RAM failure

Indicates that the controller working

memory has failed.

ERR 1-Program Memory failure

Indicates a problem with the controller program.

ERR 2-Watchdog

time-out

The controller program has entered a mode whereby the controller program has stopped executing.

ERR 3-N/A

N/A

ERR 4-N/A

N/A

ERR 5-A-D failure

The controller's Analog to Digital (A-D) converter has failed.

ERR 6-IO Board failure

Internal program/update failure.

ERR 7-Controller failure

Internal version/firmware incompatible.

ERR 8-DataCORDER failure

Internal DataCORDER memory failure.

ERR 9-Controller failure

Internal controller memory failure.

In the event that a failure occurs and the display cannot be updated, the status LED will indicate the appropriate ERR code using Morse code as shown below.

            E   R    R    0 to 9

ERR0 =  .   .-.  .-.    -----

ERR1 =  .   .-.  .-.    . ----

ERR2 =  .   .-.  .-.    . . ---

ERR3 =  .   .-.  .-.    . . . --

ERR4 =  .   .-.  .-.    . . . . -

ERR5 =  .   .-.  .-.    . . . . .

ERR6 =  .   .-.  .-.    -. . . .

ERR7 =  .   .-.  .-.    --. . .

ERR8 =  .   .-.  .-.    ---. .

ERR9 =  .   .-.  .-.    ---- .

Entr StPt

Enter Set point (Press Arrow & Enter)

The controller is prompting the operator to enter a set point.

LO

Low Main Voltage (Function Codes Cd27-38 disabled and NO alarm stored.)

This message will be alternately displayed with the set point whenever the supply voltage is less than 75% of its proper value.

Table 4–7  Controller Pre-trip Test Codes

Code

Title

Description

“Auto” or “Auto1” menu includes the: P0, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2” menu includes P0, P1, P2, P3, P4, P5, P6, P7, P8, P9, P10 and rSLts. “Auto3” menu includes P0, P1, P2, P3, P4, P5, P6, P7 and P8.

P0-0

Pre-trip Initiated

All lights and display segments will be energized for five seconds at the start of the pre-trip. Since the unit cannot recognize lights and display failures, there are no test codes or results associated with this phase of pre-trip.

P1-0

Heaters Turned On

Setup: Heater must start in the OFF condition, and then be turned on. A current draw test is done after 15 seconds.

Pass/Fail Criteria: Passes if current draw change is within the range specified.

P1-1

Heaters Turned Off

Setup: Heater must start in the ON condition, and then be turned off. A current draw test is done after 10 seconds.

Pass/Fail Criteria: Passes if current draw change is within the range specified.

P2-0

Condenser Fan On

Requirements: Water pressure switch or condenser fan switch input must be closed.

Setup: Condenser fan is turned ON, a current draw test is done after 15 seconds.

Pass/Fail Criteria: Passes if current draw change is within the range specified.

P2-1

Condenser Fan Off

Setup: Condenser fan is turned OFF, a current draw test is done after 10 seconds.

Pass/Fail Criteria: Passes if current draw change is within the range specified.

P3

Low Speed Evaporator Fans

Requirements: The unit must be equipped with a low speed evaporator fan, as determined by the Evaporator Fan speed select configuration variable.

P3-0

Low Speed Evaporator Fan Motors On

Setup: The High Speed Evaporator fans will be turned on for 10 seconds, then off for two seconds, then the low speed evaporator fans are turned on. A current draw test is done after 60 seconds.

Pass/Fail Criteria: Passes if change in current draw is within the range specified.

P3-1

Low Speed Evaporator Fan Motors Off

Setup: The Low Speed Evaporator fan is turned off, a current draw test is done after 10 seconds.

Pass/Fail Criteria: Passes if change in current draw is within the range specified.

P4-0

High Speed Evaporator Fan Motors On

Setup: The high speed evaporator fan is turned on, a current draw test is done after 60 seconds.

Pass/Fail Criteria: Passes if change in current draw is within the range specified.

P4-1

High Speed Evaporator Fan Motors Off

Setup: The high speed evaporator fan is turned off, a current draw test is done after 10 seconds.

Pass/Fail Criteria: Passes if change in current draw is within the range specified.

P5-0

Supply / Return Probe Test

Setup: The High Speed Evaporator Fan is turned on and run for eight minutes, with all other outputs de-energized.

Pass/Fail Criteria: A temperature comparison is made between the return and supply probes.

NOTE:

If this test fails, “P5-0” and “FAIL” will be displayed. If both Probe tests (this test and the PRIMARY/ SECONDARY) pass, the display will read “P5” “PASS.”

P5-1

Supply Probe Test

Requirements: For units equipped with secondary supply probe only.

Pass/Fail Criteria: The temperature difference between supply temperature sensor (STS) and supply recorder sensor (SRS) probe is compared.

If this test fails, “P5-1” and “FAIL” will be displayed. If both Probe tests (this and the SUPPLY/RETURN TEST) pass, because of the multiple tests, the display will read “P 5" “PASS.”

P5-2

Return Probe Test

Requirements: For units equipped with secondary return probe only.

Pass/Fail Criteria: The temperature difference between return temperature sensor (RTS) and return temperature sensor (RRS) probe is compared.

NOTES

1.If this test fails, “P5-2” and “FAIL” will be displayed. If both Probe tests (this test and the SUPPLY/RETURN) pass, because of the multiple tests, the display will read “P 5,” “PASS.”

2.The results of Pre-trip tests 5-0, 5-1 and 5-2 will be used to activate or clear control probe alarms.

P5-3

Evaporator Fan Direction Test

Requirements: Test P5-0 must pass before this test is run.

Setup: While the evaporator is running on high speed, the temperature differential between supply temperature sensor (STS) and return temperature sensor (RTS) probes is measured, with and without heaters energized.

Pass/Fail Criteria: Passes if differential of STS is 0.25 degree C higher than RTS.

P5-7

Primary vs Secondary Evaporator Temperature Sensor Test

Pass/Fail Criteria: Passes if secondary evaporator temperature sensor (ETS2) is within +/- 0.5 degree C of the primary evaporator temperature sensor (ETS1).

P5-8

Suction Pressure Transducer Test

Requirements: Test P5-7 must pass before this test is run.

Pass/Fail Criteria: Passes if suction pressure transducer (SPT) is within +/- 0 psi of saturation pressure at current evaporator temperature. Also passes if suction pressure transducer (SPT) is within +/- 1 psi of discharge pressure 6 hours after a power interruption.

P5-9

Suction (Evaporator) Pressure Transducer Test

Pass/Fail Criteria: Passes if suction pressure transducer (SPT) is within +/- 1.5 psi of the evaporator pressure transducer (EPT).

P5-10

Humidity Sensor Controller Configuration Verification Test

Requirements: Test P5-9 must pass before this test is run.

Test is skipped if controller is not configured for the humidity sensor and the voltage is less than 0.20 volts.

Pass/Fail Criteria: Passes if controller configuration has the humidity sensor in stalled. Fails if controller is not configured for humidity sensor and the voltage is greater than 0.20 volts.

P5-11

Humidity Sensor Installation Verification Test

Requirements: Test P5-10 must pass before this test is run.

Pass/Fail Criteria: Passes if voltage is greater than 0.20 volts for the humidity sensor. Fails if voltage is less than 0.20 volts for the humidity sensor.

P5-12

Humidity Sensor Range Check Test

Requirements: Test P5-11 must pass before this test is run.

Pass/Fail Criteria: Passes if the voltage for the humidity sensor is between 0.66 volts and 4 volts. Fails if voltage is outside of the 0.66 volt to 4 volt range.

P6-0

Discharge Thermistor Test

If alarm 64 is activated any time during the first 45 second period of

Step 1, the test fails.

P6-1

Suction Thermistor Test

Alarm is activated if suction temperature is outside of the valid range of -60°C (-76°F) to 150°C (302°F) any time during the first 45 second period of Step 1, the test fails.

P6-2

Discharge Pressure Sensor Test

If alarm 65 is activated any time during the first 45 second period of Step 1, the test fails.

P6-3

Suction Pressure Sensor Test

If alarm 66 is activated, the test fails.

P6-4

Compressor Current Draw Test

Compressor current is tested before and 10 seconds after start up. If current does not increase, the test fails. P6-7 is run at the end of P6-4. If this test fails, P6-6 is skipped.

P6-5

Compressor Leak Test

Pre-trip P6-5 ensures that the compressor holds pressure. After compressor pump up and pump down, the compressor is turned off for 62 seconds. When suction side pressure holds (less than 8 psi rise) for 10 seconds, P6-5 passes, otherwise the Compressor Leak Test fails.

P6-6 through P6-10 tests are conducted by changing the status of each individual valve and compar­ing suction pressure change and/or compressor current change with predetermined values. The tests will cause the compressor and condenser fans to cycle on and off as needed to generate the pressure required for the individual pre-trip sub tests. The compressor will start in order to build discharge pres­sure, followed by a compressor pump down sequence. At the conclusion of the compressor pump down sequence, the compressor will shut down and the valve test will start.

P6-6

Economizer Valve Test

Passes if suction pressure increases a minimum of 4 psi when the valve opens for 15 seconds.

P6-7

Digital Unloader Valve Test

Passes if pressure and current changes are within 3 seconds of DUV switch signal and either the pressure change or the current draw change is above 5 psi or above 1.5A, respectively.

P6-10

Electronic Expansion Valve Test

Pass/Fail Criteria: The test records the suction pressure during the open valve

position and passes if the suction pressure increase is above 3 psi when the valve opens for 10 seconds.

P7-0 & P8 are included with “Auto2 & Auto 3" only. P9-0 through P10 are included with “Auto2” only.

P7-0

High Pressure Switch Open

This test is skipped if the sensed ambient temperature is less than 7°C (45°F), the return air temperature is less than -17.8°C (0°F), the water pressure switch is open or the condenser fan switch is open.

Setup: With the unit running, the condenser fan is turned off and a 900 second (15 minute) timer is started. The right display shows the value of the initial sensor configured and valid out of the discharge pressure, CPC pressure, discharge temperature.

Pass/Fail Criteria: The test fails immediately if:

all three sensors are not configured or are invalid.

the ambient temperature or return air temperature sensors are invalid at the start of the test.

The test fails if:

the high pressure switch if open at the start of the test.

the high pressure switch fails to open within 15 minutes.

a valid discharge temperature exceeds 137.78°C (280°F).

a valid discharge pressure or valid condensing pressure exceeds 390 psig.

The test passes if the high pressure switch opens within the 15 minute time limit and before any of the valid and configured sensors exceed their limits.

P7-1

High Pressure Switch Closed

Requirements: Test P7-0 must pass for this test to execute. Setup: The condenser fan is started and a 60 second timer is started.

Pass/Fail Criteria: Passes the test if the high pressure switch (HPS) closes within the 60 second time limit, otherwise, it fails.

P8-0

Perishable Mode Heat Test

Setup: If the container temperature is below 15.6°C (60°F), the set point is changed to 15.6°C, and a 180-minute timer is started. The left display will read “P8-0.” The control will then heat the container until 15.6°C is reached. If the container temperature is above 15.6°C at the start of the test, then the test proceeds immediately to test P8-1 and the left display will change to “P8-1.”

Pass/Fail Criteria: The test fails if the 180 minute timer expires before the control temperature reaches set point. The display will read “P8-0,” “FAIL.”

P8-1

Perishable Mode Pulldown Test

Requirements: Control temperature must be at least 15.6°C (60°F).

Setup: The set point is changed to 0°C (32°F), and a 180-minute timer is started. The left display will read “P8-1,” the right display will show the supply air temperature. The unit will then start to pull down the temperature to the 0C set point.

Pass/Fail Criteria: The test passes if the container temperature reaches set point before the 180 minute timer expires.

P8-2

Perishable Mode Maintain Temperature Test

Requirements: Test P8-1 must pass for this test to execute. This test is skipped if the DataCORDER is not configured or not available.

Setup: A 15-minute timer is started. The unit will be required to minimize control temperature error (supply temperature minus set point) until the timer expires. The control temperature will be sampled at least once each minute starting at the beginning of P8-2.

Pass/Fail Criteria: If the average recorded temperature is within +/- 1.0°C (1.8°F) of set point, the test passes. If the average temperature is outside of the tolerance range or if the DataCORDER supply temperature probe is invalid, the test fails and the control probe temperature will be recorded as -50.0°C. P8-2 will auto-repeat by starting P8-0 over.

P9-0

Defrost Test

Setup: The defrost temperature sensor (DTS) reading will be displayed on the left display. The right display will show the supply air temperature. The unit will run FULL COOL for 30 minutes maximum until the DTT is considered closed. Once the DTT is considered closed, the unit simulates defrost by running the heaters for up to two hours, or until the DTT is considered open.

Pass/Fail Criteria: The test fails if: the DTT is not considered closed after the

30 minutes of full cooling, HTT opens when DTT is considered closed or if return air temperature rises above 49°C (120°F).

P10-0

Frozen Mode Heat Test

Setup: If the container temperature is below 7.2°C (45°F), the set point is changed to 7.2°C and a 180-minute timer is started. The control will then be placed in the equivalent of normal heating. If the container temperature is above 7.2°C at the start of the test, then the test proceeds immediately to test 10-1. During this test, the control temperature will be shown in the right display.

Pass/Fail Criteria: The test fails if the 180-minute timer expires before the control temperate reaches set point -0.3°C (0.17°F). If the test fails it will not auto-repeat. There is no pass display for this test. Once the control temperature reaches set point, the test proceeds to test 10-1.

P10-1

Frozen Mode Pulldown Test

Requirements: Control temperature must be at least 7.2°C (45°F)

Setup: The set point is changed to -17.8°C (0°F). The system will then attempt to pull down the control temperature to set point using normal frozen mode cooling. During this test, the control temperate will be shown on the right display.

Pass/Fail Criteria: If the control temperature does not reach set point -0.3°C (0.17°F) before the 180-minute timer expires the test fails and will auto-repeat by starting P10-0 over.

P10-2

Frozen Mode Maintain Temperature Test

Requirements: Test P10-1 must pass for this test to execute. This test is skipped if the DataCORDER is not configured or not available.

Setup: A 15-minute timer is started. The unit will be required to minimize return probe temperature error (supply temperature minus set point) until the timer expires. The return probe temperature will be sampled at least once each minute starting at the beginning of P10-2.

Pass/Fail Criteria: If the average recorded temperature is within +/- 1.6°C (+/- 2.9) of set point, the test passes. If the average temperature is outside of the tolerance range or if the DataCORDER return temperature probe is invalid, the test fails and the control probe temperature will be recorded as -50.0°C. P10-2 will auto-repeat by starting P10-0 over.

Table 4–8  DataCORDER Function Code Assignments

NOTE

Inapplicable Functions Display “-----”

To Access: Press ALT. MODE key

Code

Title

Description

dC1

Recorder Supply Temperature

Current reading of the supply recorder sensor.

dC2

Recorder Return Temperature

Current reading of the return recorder sensor.

dC3-5

USDA 1,2,3 Temperatures

Current readings of the three USDA probes.

dC6-13

Network Data Points 1-8

Current values of the network data points (as configured). Data point 1 (Code 6) is generally the humidity sensor and its value is obtained from the controller once every minute.

dC14

Cargo Probe 4 Temperature

Current reading of the cargo probe #4.

dC15-19

Future Expansion

These codes are for future expansion, and are not in use at this time.

dC20-24

Temperature Sensors 1-5 Calibration

Current calibration offset values for each of the five probes: supply, return, USDA #1, #2, and #3. These values are entered via the interrogation program.

dC25

Future Expansion

This code is for future expansion, and is not in use at this time.

dC26,27

S/N, Left 4, Right 4

The DataCORDER serial number consists of eight characters. Function

code dC26 contains the first four characters. Function code dC27 contains the last four characters. (This serial number is the same as the controller

serial number.)

dC28

Minimum Days Left

An approximation of the number of logging days remaining until the Data CORDER starts to overwrite the existing data.

dC29

Days Stored

Number of days of data that are currently stored in the DataCORDER.

dC30

Date of Last Trip start

The date when a Trip Start was initiated by the user. In addition, if the system goes without power for seven continuous days or longer, a trip start will automatically be generated on the next AC power up. Press and hold “ENTER” key for five seconds to initiate a “Trip Start.”

dC31

Battery Test

Shows the current status of the optional battery pack.

PASS: Battery pack is fully charged.

FAIL: Battery pack voltage is low.

dC32

Time: Hour, Minute

Current time on the real time clock (RTC) in the DataCORDER.

dC33

Date: Month, Day

Current date (month and day) on the RTC in the DataCORDER.

dC34

Date: Year

Current year on the RTC in the DataCORDER.

dC35

Cargo Probe 4 Calibration

Current calibration value for the Cargo Probe. This value is an input via the interrogation program.

Table 4–9  DataCORDER Pre-trip Result Records

Test

Title

Data

1-0

Heater On

Pass / Fail / Skip Result, Change in current for Phase A, B and C

1-1

Heater Off

Pass / Fail / Skip Result, Change in currents for Phase A, B and C

2-0

Condenser Fan On

Pass / Fail / Skip Result, Water pressure switch (WPS) - Open/Closed, Change in currents for Phase A, B and C

2-1

Condenser Fan Off

Pass / Fail / Skip Result, Change in currents for Phase A, B and C

3-0

Low Speed Evaporator Fan On

Pass / Fail / Skip Result, Change in currents for Phase A, B and C

3-1

Low Speed Evaporator Fan Off

Pass / Fail / Skip Result, Change in currents for Phase A, B and C

4-0

High Speed Evaporator Fan On

Pass / Fail / Skip Result, Change in currents for Phase A, B and C

4-1

High Speed Evaporator Fan Off

Pass / Fail / Skip Result, Change in currents for Phase A, B and C

5-0

Supply/Return Probe Test

Pass / Fail / Skip Result, STS, RTS, SRS and RRS

5-1

Secondary Supply Probe (SRS) Test

Pass / Fail / Skip

5-2

Secondary Return Probe (RRS) Test

Pass / Fail / Skip

6-0

Discharge Thermistor Test

Pass / Fail / Skip

6-1

Suction Thermistor Test

Pass / Fail / Skip

6-2

Discharge Pressure Sensor Test

Pass / Fail / Skip

6-3

Suction Pressure Sensor Test

Pass / Fail / Skip

6-4

Compressor Current Draw Test

Pass / Fail / Skip

6-5

Compressor Leak Test

Pass / Fail / Skip

6-6

Economizer Valve Test

Pass / Fail / Skip

6-7

Digital Unloader Valve Test

Pass / Fail / Skip

7-0

High Pressure Switch Closed

Pass / Fail / Skip Result, AMBS, DPT or CPT (if equipped)

Input values that component opens

7-1

High Pressure Switch Open

Pass / Fail / Skip Result, STS, DPT or CPT (if equipped)

Input values that component closes

8-0

Perishable Mode Heat Test

Pass / Fail / Skip Result, STS, time it takes to heat to 16°C (60°F)

8-1

Perishable Mode Pulldown Test

Pass / Fail / Skip Result, STS,

time it takes to pull down to 0°C (32°F)

8-2

Perishable Mode Maintain Test

Pass / Fail / Skip Result, Averaged DataCORDER supply

temperature (SRS) over last recording interval.

9-0

Defrost Test

Pass / Fail / Skip Result, DTS reading at end of test, line voltage, line frequency, time in defrost.

10-0

Frozen Mode Heat Test

Pass / Fail / Skip Result, STS, time unit is in heat.

10-1

Frozen Mode Pulldown Test

Pass / Fail / Skip Result, STS,

time to pull down unit to -17.8°C (0°F).

10-2

Frozen Mode Maintain Test

Pass / Fail / Skip Result, Averaged DataCORDER

return temperature (RRS) over last recording interval.

Table 4–10  DataCORDER Alarm Indications

To Access: Press ALT. MODE key

Code

Title

Description

dAL70

Recorder Supply Temperature Out of Range

The supply recorder sensor reading is outside of the range of -50°C to 70°C (-58°F to +158°F), or the probe check logic has determined there is a fault with this sensor.

NOTE:

The P5 Pre-trip test must be run to inactivate the alarm.

dAL71

Recorder Return Temperature Out of Range

The return recorder sensor reading is outside of the range of -50°C to 70°C (-58°F to +158°F, or the probe check logic has determined there is a fault with this sensor.

NOTE:

The P5 Pre-trip test must be run to inactivate the alarm.

dAL72-74

USDA Temperatures 1, 2, 3 Out of Range

The USDA probe temperature reading is outside of -50°C to 70°C (-58°F to +158°F range.

dAL75

Cargo Probe 4 Out of Range

The cargo probe temperature reading is outside of -50°C to 70°C (-58°F to +158°F range.

dAL76, 77

Future Expansion

These alarms are for future expansion and are not in use at this time.

dAL78-85

Network Data Point 1 - 8 Out of Range

The network data point is outside of its specified range. The DataCORDER is configured by default to record the supply and return recorder sensors. The DataCORDER may be configured to record up to eight additional network data points. An alarm number (AL78 to AL85) is assigned to each configured point. When an alarm occurs, the DataCORDER must be interrogated to identify the data point assigned. When a humidity sensor is installed, it is usually assigned to AL78.

dAL86

RTC Battery Low

The real time clock (RTC) backup battery is too low to adequately maintain the RTC reading.

dAL87

RTC Failure

An invalid time has been detected. Either the DataCorder run time hour and minute have not changed at the start of the hour, or the real time clock (RTC) time has gained or lost more than 2 minutes in the hour. This situation may be corrected by cycling the power, setting the clock or meeting the above

criteria for an hour.

dAL88

DataCORDER EEPROM Failure

A write of critical DataCORDER information to the EEPROM has failed.

dAL89

Flash Memory Error

An error has been detected in the process of writing daily data to the non-volatile FLASH memory.

dAL90

Future Expansion

This alarm is for future expansion, and is not in use at this time.

dAL91

Alarm List Full

The DataCORDER alarm queue is determined to be full (eight alarms).