Section 6
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
No power to unit |
External power source OFF |
Turn On |
Start−Stop switch OFF or defective |
Check |
|
Circuit breaker tripped or OFF |
Check |
|
Autotransformer not connected |
||
Loss of control power |
Circuit breaker OFF or defective |
Check |
Control transformer defective |
Replace |
|
Fuse (F3A/F3B) blown |
Check |
|
Start−Stop switch OFF or defective |
Check |
|
Component(s) not operating |
Evaporator fan motor internal protector open |
|
Condenser fan motor internal protector open |
||
Compressor internal protector open |
||
High pressure switch open |
||
Heat termination thermostat open |
Replace |
|
Malfunction of current sensor |
Replace |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Container |
Hot load |
Normal |
Defective box insulation or air leak |
Repair |
|
Refrigeration system |
Shortage of refrigerant |
|
Evaporator coil covered with ice |
||
Evaporator coil plugged with debris |
||
Air bypass around evaporator coil |
Check |
|
Controller set too low |
Reset |
|
Compressor service valves or liquid line shutoff valve partially closed |
Open valves completely |
|
Dirty condenser |
||
Compressor worn |
||
Current limit (function code Cd32) set to wrong value |
||
Economizer solenoid valve malfunction |
||
Digital unloader valve stuck open |
||
Electronic expansion valve |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Refrigeration system |
Abnormal pressures |
|
Abnormal temperatures |
||
Abnormal currents |
||
Controller malfunction |
||
Evaporator fan or motor defective |
||
Compressor service valves or liquid line shutoff valve partially closed |
Open valves completely |
|
Frost on coil |
||
Digital unloader valve stuck open |
||
Electronic expansion valve |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
No operation of any kind |
Start−Stop switch OFF or defective |
Check |
Circuit breaker OFF or defective |
Check |
|
External power source OFF |
Turn ON |
|
No control power |
Circuit breaker or fuse defective |
Replace |
Control Transformer defective |
Replace |
|
Evaporator fan internal motor protector open |
||
Heat relay defective |
Check |
|
Heater termination thermostat open |
||
Unit will not heat or has insufficient heat |
Heater(s) defective |
|
Heater contactor or coil defective |
Replace |
|
Evaporator fan motor(s) defective or running backwards |
||
Evaporator fan motor contactor defective |
Replace |
|
Controller malfunction |
||
Defective wiring |
Replace |
|
Loose terminal connections |
Tighten |
|
Low line voltage |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Unit fails to stop heating |
Controller improperly set |
Reset |
Controller malfunction |
||
Heater termination thermostat remains closed along with the heat relay |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Will not initiate defrost automatically |
Defrost timer malfunction (Cd27) |
|
Loose terminal connections |
Tighten |
|
Defective wiring |
Replace |
|
Defrost temperature sensor defective or heat termination thermostat open |
Replace |
|
Heater contactor or coil defective |
Replace |
|
Will not initiate defrost manually |
Keypad is defective |
Replace |
Defrost temperature sensor open |
Replace |
|
Initiates but relay (DR) drops out |
Low Line Voltage |
|
Initiates but does not defrost |
Heater contactor or coil defective |
Replace |
Heater(s) burned out |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
High discharge pressure |
Condenser coil dirty |
|
Condenser fan rotating backwards |
||
Condenser fan inoperative |
||
Refrigerant overcharge or non-condensibles |
||
Discharge service valve partially closed |
Open |
|
Electronic expansion valve (EEV) control malfunction |
Replace |
|
Low suction pressure |
Incorrect software and/or controller configuration |
Check |
Failed suction pressure transducer (SPT) or evaporator pressure transducer (EPT) |
Replace |
|
Suction service valve partially closed |
Open |
|
Filter drier partially plugged |
||
Low refrigerant charge |
||
No evaporator air flow or restricted air flow |
||
Excessive frost on evaporator coil |
||
Evaporator fan(s) rotating backwards |
||
EEV control malfunction |
Replace |
|
Failed digital unloader valve (DUV) |
Replace |
|
Suction and discharge pressures tend to equalize when unit is operating |
Compressor operating in reverse |
|
Compressor cycling/stopped |
Check |
|
Failed digital unloader valve (DUV) |
Replace |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Compressor |
Compressor start up after an extended shutdown |
Normal |
Brief chattering when manually shut down |
||
Compressor operating in reverse |
||
Loose mounting bolts or worn resilient mounts |
Tighten/Replace |
|
Loose upper mounting |
||
Liquid slugging |
||
Condenser or Evaporator Fan |
Bent, loose or striking venturi |
Check |
Worn motor bearings |
||
Bent motor shaft |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Will not control |
Incorrect software and/or controller configuration |
Check |
Defective sensor |
||
Defective wiring |
Check |
|
Low refrigerant charge |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Evaporator coil blocked |
Frost on coil |
|
Dirty coil |
||
No or partial evaporator air flow |
Evaporator fan motor internal protector open |
|
Evaporator fan motor(s) defective |
||
Evaporator fan(s) loose or defective |
||
Evaporator fan contactor defective |
Replace |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Vent not opening |
Unit not Configured for eAutoFresh Operation |
No action |
Cd43 in Off mode |
||
Wiring disconnected |
Check wiring |
|
Stepper drive defective |
||
Stepper motor defective |
||
Unit operating in frozen mode |
||
Gas Limit mode unavailable |
Check CO2 sensor |
|
Wiring disconnected |
Check wiring |
|
Unit operating in frozen mode |
||
Unable to calibrate CO2 sensor |
“Enter” Key not held for sufficient length of time |
|
CO2 outside of acceptable levels |
Check |
|
Check CO2 sensor |
||
Code 44 displays “-----” |
Unit not Configured for eAutoFresh Operation |
No action |
Check CO2 sensor |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Low suction pressure |
Incorrect software and/or controller configuration |
Check |
Failed suction pressure transducer (SPT) or evaporator pressure transducer (EPT) |
Replace |
|
Suction service valve partially closed |
Open |
|
Filter drier partially plugged |
||
Low refrigerant charge |
||
No evaporator air flow or restricted air flow |
||
Excessive frost on evaporator coil |
||
Evaporator fan(s) rotating backwards |
||
EEV control malfunction |
||
Failed digital unloader valve (DUV) |
Replace |
|
Loose or insufficiently clamped sensor |
Replace |
|
High suction pressure with low superheat |
Foreign material in valve |
|
Failed suction pressure transducer (SPT) or evaporator pressure transducer (EPT) |
Replace |
|
EEV control malfunction |
Replace |
|
Improperly seated powerhead |
Ensure powerhead is locked and in place |
|
Liquid slugging in compressor |
Failed suction pressure transducer (SPT) or evaporator pressure transducer (EPT) |
Replace |
|
Failed EEV |
Replace |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Unit will not start |
Circuit breaker (CB−1 or CB−2) tripped |
Check |
|
Autotransformer defective |
|
|
Power source not turned ON |
Check |
|
460 VAC power plug is not inserted into the receptacle |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
The compressor may start in reverse for up to 10 seconds to determine correct phase rotation if required for phase detection. |
||
Allowing the scroll compressor to operate in reverse for more than two minutes will result in internal compressor damage. Turn the start−stop switch OFF immediately. |
||
Electrical |
Incorrect wiring of compressor |
Check |
Incorrect wiring of compressor contactor(s) |
||
Incorrect wiring of current sensor |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
High discharge temperature |
Gas Cooler coil dirty |
|
Gas Cooler fan rotating backwards |
||
Gas Cooler fan inoperative |
||
Refrigerant overcharge or non-condensibles |
||
Discharge service valve partially closed |
Open |
|
Electronic expansion valve (EEV) control malfunction |
||
Failed suction pressure transducer (SPT) or evaporator pressure transducer (EPT) |
Replace |
|
Discharge temperature sensor drifting high |
Replace |
|
Failed economizer expansion valve, economizer coil, or economizer solenoid valve |
Replace |
|
Plugged economizer expansion valve, economizer coil, or economizer solenoid valve |
Replace |
|
Loose or insufficiently clamped sensor |
Replace |
Condition |
Possible Cause |
Remedy / Reference Section |
---|---|---|
Unit reads abnormal currents |
Current sensor wiring |
Check |