Section 3

DESCRIPTION

3.1General Description

3.1.1Refrigeration Unit - Front Section

The unit is designed so that the majority of the components are accessible from the front (see Figure 3.1). The unit model number, serial number and parts identification number can be found on the serial plate on the back wall of the condenser section.

3.1.2Fresh Air Makeup Vent

The function of the upper or lower makeup air vent is to provide ventilation for commodities that require fresh air circulation. A manually operated venting system is located in the upper left access panel.

The optional eAutoFresh vent system is used to moderate the atmospheric level in the container in response to cargo respiration. When transporting frozen cargo loads the vent will be closed. The upper left access panel contains the vent slide and motor assembly. It may be removed to allow entry into the evaporator section where the CO2 sensor and drive pack are located.

Figure 3.1  Refrigeration Unit - Front Section

fig120_uv.jpg 

1.Access Panel (Evap. Fan #1)

2.Fork Lift Pockets

3.Control Box

4.Unit Display

5.Key Pad

6.Remote Monitoring Receptacle

7.Start-Stop Switch, ST

8.Compressor

9.Supply Temperature Supply/Recorder Sensor Assembly (STS/SRS)

10.Economizer

11.Ambient Temperature Sensor (AMBS)

12.Power Cables and Plug (Location)

13.Autotransformer

14.Condenser Grille

15.Upper Fresh Air Makeup Vent Panel (Evap. Fan #2)

- - - - -

3.1.3Evaporator Section

The evaporator section is shown below. The evaporator fans circulate air through the container by pulling it in the top of the unit, directing it through the evaporator coil where it is heated or cooled, and discharging it at the bottom.

If the unit is provisioned for XtendFRESH or equipped with eAutoFresh, system components are mounted in addition to the standard refrigeration unit components. The stepper motor component is installed in the vent; the air filter, CO2 sensor, stepper motor drive and CO2 sensing lines are installed on the rib of the upper grill.

Most evaporator components are accessible by removing the upper rear panel (as shown in the illustration) or by removing the evaporator fan access panels (see Figure 3.2).

Figure 3.2  Evaporator Section

fig121_uv.jpg 

1.Evaporator Fan Motor #1 (EM1)

2.Return Recorder Sensor / Temperature Sensor (RRS/RTS)

3.Humidity Sensor (HS)

4.Evaporator Fan Motor #2 (EM2)

5.Evaporator Coil Heaters (Underside of Coil)

6.Evaporator Coil

7.Electronic Expansion Valve (EEV)

8.Evaporator Temperature Sensors (Location) (ETS1 & ETS2)

9.Interrogator Connector (Rear) (ICR)

10.USDA Probe Receptacle PR2

11.USDA Probe Receptacle PR1

12.USDA Probe Receptacle PR3

13.Cargo Probe Receptacle PR4

- - - - -

3.1.4Compressor Section

The compressor section includes the compressor, digital loader valve (DLV), digital unloader valve (DUV), high pressure switch (HPS), discharge pressure transducer (DPT), evaporator pressure transducer (EPT) and the suction pressure transducer (SPT).

The supply temperature sensor and supply recorder sensor are located to the left of the compressor.

Figure 3.3  Compressor Section

fig122_uv.jpg 

1.Compressor

2.Compressor Discharge Temperature Sensor (CPDS) (Location)

3.Discharge Connection

4.Suction Connection (Location)

5.Compressor Terminal Box

6.Oil Drain (Location)

7.Economizer Connection

8.Discharge Pressure Transducer (DPT)

9.DUV/DLV Connection

10.Digital Loader Valve (DLV)

11.Suction Pressure Transducer (SPT)

12.Evaporator Pressure Transducer (EPT)

13.High Pressure Switch (HPS)

14.Discharge Service Valve

15.Suction Service Valve

16.Supply Temperature/Supply Recorder Sensor Assembly (STS/SRS)

17.Warning Label

18.Digital Unloader Valve (DUV)

- - - - -

3.1.5Air-Cooled Condenser Section

The air-cooled condenser section consists of the condenser fan, condenser coil, receiver, liquid line service valve, filter drier, fusible plug, economizer, economizer expansion valve, economizer solenoid valve (ESV), and sight glass/moisture indicator.

The condenser fan pulls air from around the coil and discharges it horizontally through the condenser fan grille.

Figure 3.4  Air-Cooled Condenser Section

fig123_uv.jpg 

1.Grille and Venturi Assembly

2.Condenser Fan

3.Condenser Coil Cover

4.Condenser Coil

5.Condenser Fan Motor

6.Receiver

7.Sight Glass

8.Filter Drier

9.Economizer

10.Economizer Solenoid Valve (ESV)

11.Economizer Expansion Valve

12.Warning Label (location)

13.Service Access Valve

14.Liquid Level/Moisture Indicator

- - - - -

3.1.6Water-Cooled Condenser Section

The unit may contain a water-cooled condenser (WCC) installed as an option. When operating on the water-cooled condenser, the condenser fan is deactivated by a water pressure switch or condenser fan switch.

The brazed plate water-cooled condenser section (Figure 3.5) consists of the brazed plate water-cooled condenser (WCC), water couplings, a water pressure switch and a fusible plug. The receiver is retained in this configuration and the brazed plate heat exchanger is placed between the air-cooled condenser and the receiver.

Figure 3.5  Brazed-Plate Water-Cooled Condenser

Fig_wcc.jpg 

1.Water-Cooled Condenser (WCC)

2.Coupling - Water In

3.Self Draining Coupling - Water Out

4.Water Pressure Switch (WPS)

- - - - -

3.1.7Control Box Section

The control box (Figure 3.6) includes: the manual operation switches, circuit breaker (CB-1), compressor, fan and heater contactors, control power transformer, fuses, key pad, display module, current sensor module, controller module and the communications interface module.

3.1.8Communications Interface Module

The communications interface module is a slave module which allows communication between the refrigeration unit and a ship system master central monitoring station. The module will respond to communication and return information over the ships main power line. Refer to the master system technical manual for further information.

Figure 3.6  Control Box Section

fig124_uv.jpg 

1.Compressor Contactor - CH

2.Compressor Phase A Contactor - PA

3.Compressor Phase B Contactor - PB

4.Heater Contactor - HR

5.Controller/DataCORDER Module (Controller)

6.Remote Monitoring Receptacle

7.Start-Stop Switch, ST

8.Controller Battery Pack (Standard Location)

9.Control Transformer

10.High Speed Evaporator Fan Contactor - EF

11.Low Speed Evaporator Fan Contactor - ES

12.Condenser Fan Contactor - CF

13.Circuit Breaker - 460V

14.Current Sensor Module

15.Condenser Fan Low Speed - LC

16.Condenser Fan (High Speed Shorting) - FS

- - - - -

3.2Refrigeration System Data

 

Table 3–1  Refrigeration System Data

Compressor / Motor Assembly

Model Number

ZMD26K2E-TFD-274

Weight (With Oil)

42.9 kg (95 lb)

Approved Oil

Uniqema Emkarate RL-32-3MAF

Oil Charge

1774 ml (60 ounces)

Electronic Expansion Valve Superheat (Evaporator)

Verify at -18°C (0°F) container box tempera­ture

4.4 to 6.7°C (8 to 12°F)

High Pressure Expansion Valve (HPXV)

Verify at -18°C (0°F) container box tempera­ture

4.4 to 11.1°C (8 to 20°F)

Heater Termination Thermostat (HTT)

Opens

54° (+/- 3) C = 130   ° (+/- 5) F

Closes

38° (+/- 4) C = 100° (+/- 7) F

High Pressure Switch (HPS)

Cut-Out

(+/- 1.0) kg/cm2 = 350 (+/- 10) psig

Cut-In

(+/- 0.7) kg/cm2 = 250 (+/- 10) psig

EXPLOSION HAZARD: Failure to follow this WARNING can result in death, serious personal injury and / or property damage.

Never use air or gas mixtures containing oxygen (O2) for leak testing or operating the product.

Charge Only With R-134a: Refrigerant must conform to AHRI Standard 700 specification.

Refrigerant

R-134a

Conforming to AHRI standard 700 specifica­tions.

Charge water-cooled condenser or receiver according to nameplate specifications to ensure optimal unit performance.

Refrigerant Charge

Receiver

4.54kg (10 lbs)

Fusible Plug

Melting Point

99°C = (210°F)

Torque

6.2 to 6.9 mkg (45 to 50 ft-lbs)

Rupture Disc

Bursts at

35 +/- 5% kg/cm2 = (500 +/- 5% psig)

Torque

6.2 to 6.9 mkg (45 to 50 ft-lbs)

Unit Weight

Refer to unit model number plate.

Water Pressure Switch

Cut-In

0.5 +/- 0.2 kg/cm2 (7 +/- 3 psig)

Cutout

1.6 +/- 0.4 kg/cm2 (22 +/- 5 psig)

 

3.3Electrical System Data

Circuit Breaker

CB-1 (25 amp)

Trips at 29 amps

CB-2 (50 amp)

Trips at 62.5 amps

CB-3 (70 amp)

Trips at 87.5 amps

Compressor Motor

Full Load Amps (FLA)

13 amps @ 460 VAC

Condenser Fan Motor

 

380 VAC/3 PH/50 Hz

460 VAC/3 PH/60 Hz

Full Load Amps, High Speed

0.73

0.80

Full Load Amps, Low Speed

.42

.44

RPM, High Speed

1425 rpm

1725 rpm

RPM, Low Speed

720 rpm

850 rpm

Voltage and Frequency

360 - 460 VAC +/-2.5Hz

400 - 506 VAC +/-2.5Hz

Bearing Lubrication

Factory lubricated, additional grease not required.

Rotation

CW when viewed from shaft end.

Evaporator Coil Heaters

Number of Heaters

6

Rating

750 watts +5/-10% each @ 230 VAC

Resistance (cold)

6.8 to 77.2 ohms @ 20°C (68°F)

Type

Sheath

Evaporator Fan Motors

 

380 VAC/3 PH/50 Hz

460 VAC/3 PH/60 Hz

Full Load Amps
High Speed

1.07

0.9

Full Load Amps
Low Speed

0.47

0.47

Rotations Per Minute
High Speed

2850 rpm

3450 rpm

Rotations Per Minute
Low Speed

1425 rpm

1725 rpm

Voltage and Frequency

360 - 460 VAC +/- 1.25Hz

400 - 500 VAC +/- 1.5Hz

Bearing Lubrication

Factory lubricated, additional grease not required

Rotation

CW when viewed from shaft end

Fuses

Control Circuit

7.5 amps (F3A,F3B)

Controller / DataCORDER

5 amps (F1 & F2)

Emergency Bypass

10 amps (FEB)

Vent Position Sensor (VPS)

Electrical Output

0.5 VDC to 4.5 VDC over 90 degree range

Supply Voltage

5 VDC +/- 10%

Supply Current

5 mA (typical)

Solenoid Valve Coils (ESV/USV) 24 VAC

Nominal Resistance @ 77°F (25°C)

7.7 ohms +/- 5%

Maximum Current Draw

0.7 amps

DLV Coil 12 VDC

Nominal Resistance @ 68°F (20°C)

14.8 ohms +/- 5%

DUV Coil 24VAC

Nominal Resistance @ 68°F (20°C)

15.5 ohms +/- 5%

EEV Nominal Resistance

Coil Feed to Ground (Gray Wire)   

47 ohms

Coil Feed to Coil Feed   

95 ohms

Humidity Sensor

Orange wire

Power

Red wire

Output

Brown wire

Ground

Input voltage

5 VDC

Output voltage

0 to 3.3 VDC

Output voltage readings verses relative humidity (RH) percentage:

30%

0.99 V

50%

1.65 V

70%

2.31 V

90%

2.97 V

Controller

Setpoint Range

-35 to +30°C (-31 to +86°F)

3.4Safety and Protective Devices

Unit components are protected from damage by safety and protective devices listed in Table 3–1. These devices monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition occurs.

Open safety switch contacts on either or both of devices IP-CP or HPS will shut down the compressor.

Open safety switch contacts on device IP-CM will shut down the condenser fan motor.

The entire refrigeration unit will shut down if one of the following safety devices open: (a) circuit breaker(s); (b) fuse (F3A/F3B, 7.5A); or (c) evaporator fan motor internal protector(s) - (IP).

Table 3–2  Safety and Protective Devices

Unsafe Condition

Device

Device Setting

Excessive current draw

Circuit Breaker (CB-1, 25 amp) - Manual Reset

Trips at 29 amps (460 VAC)

Circuit Breaker (CB-2, 50 amp) - Manual Reset

Trips at 62.5 amps (230 VAC)

Circuit Breaker (CB-2, 70 amp) - Manual Reset

Trips at 87.5 amps (230 VAC)

Excessive current draw in the control circuit

Fuse (F3A & F3B)

7.5 amp rating

Excessive current draw by the controller Fuse

Fuse (F1 & F2)

5 amp rating

Excessive current draw by the Emergency Bypass module

Fuse (FEB)

10 amp rating

Excessive condenser fan motor winding temperature

Internal Protector (IP-CM) - Automatic Reset

N/A

Excessive compressor motor winding temperature

Internal Protector (IP-CP) - Automatic Reset

N/A

Excessive evaporator fan motor(s) winding temperature

Internal Protector(s) (IP-EM) - Automatic Reset

N/A

Abnormal pressures/temperatures in the high refrigerant side

Fusible Plug - Used on the Receiver

99°C = (210°F)

Rupture Disc - Used on the Water-Cooled Condenser

35 kg/cm2 = (500 psig)

Abnormally high discharge pressure

High Pressure Switch (HPS)

Opens at 25 kg/cm2 (350 psig)

3.5Refrigeration Circuit

3.5.1Standard Operation

Starting at the compressor, (see Figure 3.7, upper schematic) the suction gas is compressed to a higher pressure and temperature.

The refrigerant gas flows through the discharge line and continues into the air-cooled condenser. When operating with the air-cooled condenser active, air flowing across the coil fins and tubes cools the gas to saturation temperature. By removing latent heat, the gas condenses to a high pressure/high temperature liquid and flows to the receiver, which stores the additional charge necessary for low temperature operation.

The liquid refrigerant continues through the liquid line, the filter drier (which keeps refrigerant clean and dry) and the economizer (not active during standard operation) to the electronic expansion valve (EEV).

As the liquid refrigerant passes through the variable orifice of the EEV, the pressure drops to suction pressure. In this process some of the liquid vaporizes to a gas (flash gas), removing heat from the remaining liquid. The liquid exits as a low pressure, low temperature, saturated mix. Heat is then absorbed from the return air by the balance of the liquid, causing it to vaporize in the evaporator coil. The vapor then flows through the suction tube back to the compressor.

During the standard mode of operation, the normally closed valves, digital loader valve (DLV) and digital unloader valve (DUV), control the system refrigerant flow and capacity by loading and unloading the compressor in frequent discrete time intervals. The DLV and DUV operate in opposition to each other such that when the DLV is closed the DUV is open and vice versa. The valves cycle on a fixed duty cycle so that maximum capacity occurs when the DLV is open 100% of the time and the DUV is open 0% and minimum capacity is when the DLV is open 0% of the time and the DUV 100% of the time. If the system capacity has been decreased to the lowest allowable capacity, the unit will enter a trim heat mode of operation, during which the controller will pulse the evaporator heaters in sequence with the compressor digital signal in order to absorb the excess capacity.

3.5.2Economized Operation

In the economized mode, (see Figure 3.8) the frozen and pull down capacity of the unit is increased by sub- cooling the liquid refrigerant entering the electronic expansion valve. Overall efficiency is increased because the gas leaving the economizer enters the compressor at a higher pressure, therefore requiring less energy to compress it to the required condensing conditions.

Liquid refrigerant for use in the economizer circuit is taken from the main liquid line as it leaves the filter drier. The flow is activated when the controller energizes the economizer solenoid valve (ESV).

The liquid refrigerant flows through the ESV to the economizer expansion valve internal passages, absorbing heat from the liquid refrigerant flowing to the electronic expansion valve. The resultant “medium” temperature/pressure gas enters the compressor at the economizer port fitting.

3.5.3Economizer Expansion Valve

The microprocessor controls the superheat leaving the economizer expansion valve (EXV). From the EXV the refrigerant flows through the internal passages of the economizer heat exchanger, absorbing heat from the refrigerant flowing to the EEV. The resultant “medium” temperature/pressure gas enters the compressor at the economizer port fitting.

Figure 3.7  Refrigeration Circuit Schematic - Standard Operation

circuit-diagram-standard.jpg 

1.Compressor

2.Discharge Service Valve

3.Discharge Pressure Transducer (DPT)

4.Condenser

5.Receiver

6.Receiver Sight Glass

7.Fusible Plug

8.Receiver Liquid Level / Moisture Indicator

9.Liquid Line Service Valve

10.Filter Drier

11.Economizer

12.Economizer Solenoid Valve (ESV)

13.Economizer Expansion Valve (EXV)

14.Economizer Expansion Valve (EXV) Sensing Bulb

15.Economizer Connection

16.Electronic Expansion Valve (EEV)

17.Evaporator

18.Evaporator Temperature Sensor (ETS1)

19.Evaporator Temperature Sensor (ETS2)

20.Digital Unloader Valve (DUV)

21.Digital Loader Valve (DLV)

22.Evaporator Pressure Transducer (EPT)

23.Suction Pressure Transducer (SPT

24.Suction Service Valve

- - - - -

Figure 3.8  Refrigeration Circuit Schematic - Economized Operation

circuit-diagram-economized.jpg 

1.Compressor

2.Discharge Service Valve

3.Discharge Pressure Transducer (DPT)

4.Condenser

5.Receiver

6.Receiver Sight Glass

7.Fusible Plug

8.Receiver Liquid Level / Moisture Indicator

9.Liquid Line Service Valve

10.Filter Drier

11.Economizer

12.Economizer Solenoid Valve (ESV)

13.Economizer Expansion Valve (EXV)

14.Economizer Expansion Valve (EXV) Sensing Bulb

15.Economizer Connection

16.Electronic Expansion Valve (EEV)

17.Evaporator

18.Evaporator Temperature Sensor (ETS1)

19.Evaporator Temperature Sensor (ETS2)

20.Digital Unloader Valve (DUV)

21.Digital Loader Valve (DLV)

22.Evaporator Pressure Transducer (EPT)

23.Suction Pressure Transducer (SPT

24.Suction Service Valve

- - - - -

Figure 3.9  Refrigeration Circuit Schematic - Water-Cooled Condenser

circuit-diagram-wcc-braze-plate.jpg 

1.Compressor

2.Discharge Service Valve

3.Discharge Pressure Transducer (DPT)

4.Condenser

5.Water-Cooled Condenser

6.Coupling (Water In)

7.Water Pressure Switch

8.Coupling (Water Out)

9.Receiver

10.Receiver Sight Glass

11.Fusible Plug

12.Receiver Liquid Level / Moisture Indicator

13.Liquid Line Service Valve

14.Filter Drier

15.Economizer

16.Economizer Solenoid Valve (ESV)

17.Economizer Expansion Valve (EXV)

18.Economizer Expansion Valve (EXV) Sensing Bulb

19.Economizer Connection

20.Electronic Expansion Valve (EEV)

21.Evaporator

22.Evaporator Temperature Sensor (ETS1)

23.Evaporator Temperature Sensor (ETS2)

24.Digital Unloader Valve (DUV)

25.Digital Loader Valve (DLV)

26.Evaporator Pressure Transducer (EPT)

27.Suction Pressure Transducer (SPT

28.Suction Service Valve

- - - - -